Mitsubishi Electric PURY-RP200 Service Handbook page 111

Hide thumbs Also See for PURY-RP200:
Table of Contents

Advertisement

[ VI Refrigerant Circuit ]
Part
Symbols
name
(functions)
Thermis-
TH3
tor
(Pipe
temperature)
TH7
(Outdoor tem-
perature)
TH5
TH6
THHS
Inverter
heat sink tem-
perature
Sole-
SV1a
noid
Discharge-suc-
valve
tion
bypass
SV2
SV4a - SV4d
Heat
exchanger
capacity control
SV5b
Heat
exchanger
capacity control
SV5c
SV6
(Intermediate
pressure con-
trol)
SV8
(Controls the
refrigerant flow
during automat-
ic refrigerant
charging opera-
tion.)
SV9
HWE10020
Notes
Usage
Controls defrosting during heating
operation
1) Detects outdoor air tempera-
ture
2) Controls fan operation
Fan operated on the 63LS and
TH5 values.
Controls defrosting during heating
operation
Controls inverter cooling fan
based on THHS temperature
1) High/low pressure bypass at
start-up and stopping, and
capacity control during low-
load operation
2) High-pressure-rise preven-
tion
Controls outdoor unit heat ex-
changer capacity
Prevents high-pressure-rise
Controls defrost cycle
Allows the refrigerant to pass
through the bypass pipe to pre-
vent an accumulation of liquid re-
frigerant
Intermediate-pressure-rise pre-
vention
Opens or closes as necessary
during automatic refrigerant
charging operation.
High-pressure-rise prevention
- 102 -
Specifications
Degrees Celsius
R
= 15k
0
R
= 3460
0/80
1
1
exp
R = 15
3460
t
273
0°C[32°F] :15kohm
10°C[50°F] :9.7kohm
20°C[68°F] :6.4kohm
25°C[77°F] :5.3kohm
30°C[86°F] :4.3kohm
40°C[104°F] :3.1kohm
Degrees Celsius
R
= 17k
50
R
= 4016
25/120
1
1
R = 17
exp
4016
t
323
0°C[32°F] :161kohm
10°C[50°F] :97kohm
20°C[68°F] :60kohm
25°C[77°F] :48kohm
30°C[86°F] :39kohm
40°C[104°F] :25kohm
AC220 - 240V
Open while being powered/
closed while not being pow-
ered
AC220 - 240V
Closed while being powered/
open while not being powered
AC220 - 240V
Open while being powered/
closed while not being pow-
ered
AC220 - 240V
Closed while being powered/
open while not being powered
AC220 - 240V
Open while being powered/
closed while not being pow-
ered
AC220 - 240V
Open while being powered/
closed while not being pow-
ered
Check method
Resistance
check
Continuity
check with a
tester
GB