Mitsubishi Electric PURY-RP200 Service Handbook page 122

Hide thumbs Also See for PURY-RP200:
Table of Contents

Advertisement

[ VII Control ]
Switch
1
2
Model selection
3
4
Low-noise mode se-
5
lection
SW5
6
7
Model selection
8
9
10
1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF for a reason.
2) When set to the capacity priority mode and if the following conditions are met, the quiet mode will terminate, and the unit will
go back into the normal operation mode.
Cooling-only/Cooling-main: Outside temperature is high or high pressure is high.
Heating-only/Heating-main: Outside temperature is low or low pressure is low.
3) The factory settings for dipswitches SW3-7 and SW4-7 are ON. The table below summarizes the factory settings for SW5-1
through SW5-4, and SW5-7. The factory settings for all other dipswitches are OFF. Switching SW4-7 to OFF during the oil
recovery operation does not stop the oil recovery operation, which is scheduled to last for 3 hours and half.
4) The refrigerant oil recovery operation can be cancelled and normal operation can be started if Stage 3 in the cooling mode or
Stage 4 in the heating mode has been completed. To cancel the operation, set the SW4-7 to OFF.
1
OFF
ON
OFF
(2) INV board
Functions are switched with the following connector.
Connector
CN6 short-
Enabling/disabling the following error
circuit con-
detection functions;
nector
ACCT sensor failure
(5301 Detail No. 115)
ACCT sensor circuit failure
(5301 Detail No.117)
IPM open/ACCT erroneous wiring
(5301 Detail No. 119)
Detection of ACCT erroneous wiring
(5301 Detail No.120)
CN6 short-circuit connector is mated with the mating connector.
Leave the short-circuit connector on the mating connector during normal operation to enable error detection and protect the
equipment from damage.
HWE10020
Function according to switch setting
Function
See the table below (Note 3)
Capacity priority
mode(Note 2)
-
See the table below (Note 3)
-
-
-
SW 5
2
3
ON
OFF
ON
OFF
OFF
ON
Function
OFF
ON
Low-noise mode
-
-
-
-
4
7
OFF
ON
RP200YJM model
OFF
ON
RP250YJM model
OFF
ON
RP300YJM model
Function according to connec-
tor
Enabled
Error detec-
Error detec-
tion enabled
tion disable
(No load op-
eration is pos-
sible.)
- 113 -
Switch setting timing
OFF
Before being energized
Before being energized
-
Before being energized
-
-
-
model
Setting timing
Disabled
Enabled
Anytime after power on
ON
-
-
-
-
Disabled
GB