Functions Settings - FujiFilm MEH531 Brochure

Frenic multi series high performance compact inverters
Table of Contents

Advertisement

Functions Settings

■ Functions Settings
●E codes: Extension Terminal Functions
Func.
Name
Code
Frequency Arrival Delay Time
Frequency Arrival
(hysteresis width)
Frequency Detection (FDT)
(Detection level)
(hysteresis width)
Overload Early Warning /Current Detection
(Level)
(Timer)
Current detection 2
(Level)
(Timer)
Coefficient for Constant Feeding Rate Time
PID Display Coefficient A
B
LED Display filter
LED Monitor
(Item selection)
LCD Monitor
*4
(Item selection)
(Language selection)
(Contrast control)
LED Monitor
(Speed monitor item)
Coefficient for Speed Indication
Display Coefficient for Input Watt-hour Data
Keypad (Menu display mode)
Terminal [C1] Signal Definition
(C1/V2 Function)
Terminal [12] Extended Function
Terminal [C1] Extended Function (C1 function)
Terminal [C1] Extended Function (V2 function)
Reference Loss Detection (Continuous running frequency)
Terminal [FWD] Function
Terminal [REV] Function
Data setting range
0.01 to 10.00
0.0 to 10.0
0.0 to 400.0
0.0 to 400.0
0.00 : Disable Current value of 1 to 200% of the inverter rated current
0.01 to 600.00
*1
0.00 : Disable Current value of 1 to 200% of the inverter rated current
0.01 to 600.00
*1
0.000 to 9.999
-999 to 0.00 to 9990
*1
-999 to 0.00 to 9990
*1
0.0 to 5.0
0: Speed monitor (select by E48)
3: Output current
4: Output voltage
8: Calculated torque
9: Input power
10: PID command
12: PID feedback amount
13: Timer
14: PID output
15: Load factor
16: Motor output
21: Present pulse position
22: Deviation of pulse position
0: Running status, rotational direction and operation guide
1: Bar charts for output frequency, current and calculated torque
0 : Japanese
1 : English
2 : German
3 : French
4 : Spanish
5 : Italian
0 (Low) to 10 (High)
0: Output frequency (Before slip compensation)
1: Output frequency (After slip compensation)
2: Reference frequency
3: Motor speed in r/min
4: Load shaft speed in r/min
5: Line speed in m/min
6: Constant feeding rate time
0.01 to 200.00
*1
0.000 (Cancel/reset) 0.001 to 9999
0: Function code data editing mode (Menus #0 and #1)
1: Function code data check mode (Menu #2)
2: Full-menu mode (Menus #0 through #6)
0: Current input (C1 function), 4 to 20 mADC
1: Voltage input (V2 function), 0 to +10 VDC
Selecting function code data assigns the corresponding function to terminals [12] and [C1] (C1/V2 function) as listed below.
0: None
1: Auxiliary frequency command 1
2: Auxiliary frequency command 2
3: PID command 1
5: PID feedback amount
0: Decelerate to stop 20 to 120 999: Disable
Selecting function code data assigns the corresponding function to terminals [FWD] and [REV] as listed below.
0 (1000)
: Select multi-frequency
1 (1001)
: Select multi-frequency
2 (1002)
: Select multi-frequency
3 (1003)
: Select multi-frequency
4 (1004)
: Select ACC/DEC time
6 (1006)
: Enable 3-wire operation
7 (1007)
: Coast to a stop
8 (1008)
: Reset alarm
9 (1009)
: Enable external alarm trip
10 (1010)
: Ready for jogging
11 (1011)
: Select frequency command 2/1
12 (1012)
: Select motor 2/motor 1
13
: Enable DC braking
14 (1014)
: Select torque limiter level
17 (1017)
: UP (Increase output frequency)
18 (1018)
: DOWN (Decrease output frequency)
19 (1019)
: Enable data change with keypad
20 (1020)
: Cancel PID control
21 (1021)
: Switch normal/inverse operation
24 (1024)
: Enable communications link via RS-485 or field bus
25 (1025)
: Universal DI
26 (1026)
: Enable auto search for idling motor speed at starting
27 (1027)
: Speed feedback control switch
30 (1030)
: Force to stop
33 (1033)
: Reset PID integral and differential components [PID-RST]
34 (1034)
: Hold PID integral component
Data
Min.
Unit
Default setting
copy
*2
0.01
s
Y
0.1
Hz
Y
0.1
Hz
Y
0.1
Hz
Y
0.01
A
100% of the motor rated current
Y1Y2
0.01
s
Y
0.01
A
100% of the motor rated current
Y1Y2
0.01
s
Y
0.001
-
Y
0.01
-
Y
0.01
-
Y
0.1
s
Y
-
-
Y
-
-
Y
-
-
Y
1
-
Y
-
-
Y
0.01
-
Y
0.001
-
Y
-
-
Y
-
-
Y
-
-
Y
-
-
Y
-
-
Y
1
%
Y
-
-
Y
[SS1]
-
-
Y
[SS2]
[SS4]
[SS8]
[RT1]
[HLD]
[BX]
[RST]
[THR]
[JOG]
[Hz2/Hz1]
[M2/M1]
[DCBRK]
[TL2/TL1]
[UP]
[DOWN]
[WE-KP]
[Hz/PID]
[IVS]
[LE]
[U-DI]
[STM]
[PG/Hz]
[STOP]
[PID-HLD]
0.10
2.5
60.0
1.0
10.00
10.00
0.000
100
0.00
0.5
0
0
1
5
0
30.00
0.010
0
0
0
0
0
999
98
99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents