Fireplace Installation; Check Gas Type - Monessen Hearth KSTDV500 Installation And Operating Instructions Manual

Kstdv series direct vent gas fireplace
Table of Contents

Advertisement

KSTDV Series Gas Fireplace

checK GaS Type

Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install
fireplace. See dealer where you purchased the fireplace for proper fireplace according to your gas
type.
InSTallInG GaS pIpInG To FIreplace locaTIon
a qualified installer or service person must
connect appliance to gas supply. Follow
all local codes.
InSTallaTIon ITeMS neeDeD
Before installing fireplace and burner system, make sure you have the items listed below.
External regulator
(supplied by installer)
Equipment shutoff valve*
approved flexible gas line with gas connector (if allowed by local codes — not provided)
*
A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge
connection. Purchase the CSA design-certified equipment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce
incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of water. If you do not
reduce incoming gas pressure, burner system regulator damage could occur. Install external regulator with the vent
pointing down as shown in Figure 23. Pointing the vent down protects it from freezing rain or sleet.
External
Regulator
Figure 23 -
External Regulator with Vent Pointing Down
(Propane/LP Only)
FP1977
external regulator
20
Piping (check local codes)
Test gauge connection*
Tee joint
100 gal. (min)
Propane/LP
Supply Tank
Vent Pointing
Down
FP1977

FIreplace InSTallaTIon

For propane/lp units, never connect
fireplace directly to the propane/lp
supply. This burner system requires an
external regulator (not supplied). Install
the external regulator between the burner
system and propane/lp supply.
Sealant (resistant to propane/LP gas)
• Sediment trap (recommended)
Pipe wrench
use only new black iron or steel pipe.
Internally tinned copper or copper tubing
can be used per national Fuel code, Section
2.6.3, providing gas meets hydrogen sulfide
limits, and where permitted by local codes.
Gas piping system must be sized to provide
minimum inlet pressure (listed on data
plate) at the maximum flow rate (BTu/hr).
undue pressure loss will occur if the pipe
is too small.
external regulators may be necessary for
natural gas. one- or two-pound systems
will damage this appliance and may cause
fire hazard.
When using copper or flex connectors use only fittings
approved for gas connections. The gas control inlet is
3/8" NPT.
73D4125