SIMOVERT P 6SE21 Series Inverters
Connection
POWER TERMINALS: TERMINAL BLOCK X1
Single Phase Input Units:
M
3
Three Phase Input Units:
M
3
DC – Output
DC + Output
o
Use Class 1 60/75
C copper wire only. The tightening torque for field wiring terminals is 1.5 Nm (M4).
CONTROL TERMINALS: TERMINAL BLOCK X11
=
24 V
+
5 k
+
=
X11.2
Tacho
X11.2
Figure 3: Connection Diagram
Siemens plc 1995
Terminal
Labelling Function, Data, Notes
U1
X1.L1
Mains
N1
X1.N
PE
X1.
Ground
PE
X1.
Ground
U2
X1.U
Motor connection
V2
X1.V
W2
X1.W
U1
X1.L1
Mains connection
V1
X1.L2
W1
X1.L3
PE
X1.
Ground
PE
X1.
Ground
U2
X1.U
Motor connection
V2
X1.V
W2
X1.W
X1.–
Connections for Braking Module (EBM)
X1.+
X11.1
0 V
X11.2
+15 V
X11.3
Run/Stop
X11.4
Trip
X11.5
Forward/Reverse
X11.6
+10 V Ref.
X11.7
0...10 V
X11.8
0 V
X11.9
0 (4)...20 mA
X11.10
0 V
X11.11
0...10 V
max. load 5 mA
X11.12
0...50 V
X11.13
Jog
X11.14
A
X11.15
B
X11.16
'P' Button connection
X11.17
' ' Button connection
X11.18
' ' Button connection
X11.19
NO
X11.20
COM
X11.21
NC
X11.22
0 V
Operating Instructions
1AC 220 – 240 V +/–10% 50/60 Hz
3AC 0 V ... Line voltage
0.0 ... 400 Hz
3AC 380 – 500 V +/–10%
50/60 Hz
3AC 0 V ... Line voltage
0.0 ... 400 Hz
100 k
connection to ground
Level or edge–triggered (P05)
Can be used in conjunction with Run/Stop
and with PTC
Closed = reverse
Reference voltage for potentiometer
Frequency setpoint (voltage) (P04)
Frequency setpoint (current) (P04)
Frequency/Output current indication
(10 V
f
/I
)
max
max
Tachometer input
Jog speed set by parameter P12
RS485 Serial I/O connection
Fault indication
(energised during normal operation)
G85139–A1615–U156–A
English