Fault Relay - Siemens Simovert P 6SE21 Series Operating Instructions Manual

Table of Contents

Advertisement

SIMOVERT P 6SE21 Series Inverters
Fault Code
Cause
Control board fault.
Parameter P25 set above
maximum frequency P08 or below
minimum frequency P07.
Parameter P26 set above
maximum frequency P08 or below
minimum frequency P07.
Parameter P27 set above
maximum frequency P08 or below
minimum frequency P07.
Parameter P28 set above
maximum frequency P08 or below
minimum frequency P07.
Inverter externally tripped via X11.4
input.
Figure 5: Fault Code Table (Sheet 2 of 2)
If a fault indication has been observed and the corrective action implemented, the inverter can be reset by applying a
STOP (low) signal to the run/stop input (terminal X11.3) followed by a RUN (high) signal to the same input.
Alternatively, the incoming mains voltage can be switched off and then switched on again.

5.5 Fault Relay

A single pole changeover relay is provided to indicate a fault. It is normally energised when the inverter is powered and
operating or stopped. If a fault condition occurs, the relay will be de–energised. The contacts of the relay are connected
to terminals X11.19 (normally open, de–energised), X11.20 (common) and X11.21 (normally closed, de–energised) on
the control board.
Siemens plc 1995
Corrective Action
Disconnect the inverter from the input power supply and then reconnect.
Change parameter P25, P08 or P07.
Change parameter P26, P08 or P07.
Change parameter P27, P08 or P07.
Change parameter P28, P08 or P07.
Clear external trip on X11.4 and restart the inverter.
English
Operating Instructions
G85139–A1615–U156–A
02.95
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents