General Safety Information; Installation Checklist; Clearances To Combustibles - Regency ULTIMATE U39 Owners & Installation Manual

Direct vent freestanding gas stove
Hide thumbs Also See for ULTIMATE U39:
Table of Contents

Advertisement

4) This appliance is Listed for bedroom
installations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
5) This appliance is Listed for Alcove
installations, maintain minimum Alcove
clearances as follows, minimum width of
48" (1219mm), a maximum depth of 36"
(914mm), and minimum ceiling height of
64"(1626mm).
6) We recommend that you plan your installation
on paper using exact measurements for
clearances and floor protection before
actually installing this appliance. Have a
qualifi ed building inspector review your plans
before installation.
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform with
local Canadian Electrical Code.
2) The appliance when installed, must be
electrically grounded in accordance with
local codes, or in the absence of local codes
with the current National Electrical Code,
ANSI/NFPA 70 or CSA C22.1 Canadian
Electrical Code.
3) The
appliance should be inspected for
shipping damage before use and serviced
annually by a professional service
person. More frequent cleaning may be
required due to excessive lint from carpeting,
bedding material, etc. It is imperative that
control compartments, and circulating air
passageways of the appliance be kept
clean and free from excessive lint from
carpeting.
4) See general construction and assembly
instructions. The appliance and vent should
be enclosed when installed in or passing
through a living area, where children may
come in contact with it.
5) This appliance must be connected to the
specifi ed vent and termination cap to the
outside of the building envelope. Never
vent to another room or inside a building.
Make sure that the vent is fi tted as per
the instructions starting in "Locating Your
Ultimate Gas Stove" section.
6) Inspect the venting system annually for
blockage and any signs of deterioration.
7) Venting terminals shall not be recessed into
a wall or siding.
Regency
®
U39 ULTIMATE Direct Vent Freestanding Gas Stove
8) Any safety glass removed for servicing
must be replaced prior to operating the
appliance.
9) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fi replace.
Emissions from burning wood or gas could
contain chemicals known to the State of Cali-
fornia to cause cancer, birth defects or other
reproductive harm.
INSTALLATION
CHECKLIST
1) Loate your appliance. Refer to the following
sections:
a. Locating Your Ultimate Gas Stove
b. Exterior Vent Termination Locations
c. Clearance to Combustibles
d. Combustion and Ventilation Air
2) Install Louvers.
Refer to the "Louver
Installation" section.
3) Choose a venting option and install
accordingly. Refer to the following sections
where applicable:
a. DV Stove Horizontal Vent Kit
Installation
b. Dura-Vent Termination Kit
c. Set Vent Restrictors. Refer to "Rigid
Pipe Venting Arrangement" section.
d. Converting a Class-A Metal Chimney
or Masonry Chimney to a Direct Vent
system.
4) Make gas connections. Refer to "Gas
Connection" section.
Test the pilot. Must be as per diagram. Refer
to "Pilot Adjustment" section.
5) If necessary, see the "Conversion from NG
to LPG" section and "Conversion to Lower
BTU Rating" section.
6) Test Gas Pressure. Refer to "Gas Pipe
Pressure Testing" section .
7) Install standard and optional features.
Refer to the following sections where
applicable:
a. Log Set
b. Front Door
c. Wall Thermostat
d. Remote Control
8) Final check. Refer to the "Final Check"
section.
INSTALLATION
Before leaving this unit with the customer,
the installer must ensure that the appliance is
fi ring correctly and operation fully explained
to customer.
This includes:
1) Clocking the appliance to ensure the correct
fi ring rate (rate noted on label) after burning
appliance for 15 minutes.
2) If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow
the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that
causes sooting or carboning that results
in damage is not the responsibility of the
manufacturer.
CLEARANCES TO
COMBUSTIBLES
The clearances listed are MINIMUM distances.
Measure the clearance to both the appliance
and the chimney connector. The farthest
distance is correct if the two clearances do
not coincide.
For example, if the appliance is set as indicated
in one of the fi gures but the connector is too
close, move the stove until the correct clearance
to the connector is obtained.
This appliance may be installed only with the
clearances as shown in the situations pictured.
Do not combine clearances from one type of
installation with another in order to achieve
closer clearances.
This unit can be installed on a solid combustible
surface like a wood fl oor. This unit can also be
installed directly on carpeting or vinyl when the
bottom pedestal cover plate (provided with unit)
is installed.
Use the minimum clearances shown in the
diagrams below:
U39-NG1 & U39-LP1 Clearances
A Side Wall to Unit
B Back Wall to Unit
E Side Wall to Unit
U39-NG1 & U39-LP1 Reference
Dimensions
C Back Wall to Flue Centerline 11"/280 mm
D Side Wall to Flue Centerline 20-1/2"/521 mm
F Side Wall to Flue Centerline 11"/280 mm
Minimum ceiling height is 36" / 914 mm from top
of unit.
7-1/2" / 190 mm
6" / 150 mm
2" / 50 mm