Si (Metric) Conversion Factors; Before You Begin - Modine Manufacturing PTC Installation And Service Manual

Ptc/btc series high efficiency, separated combustion gas-fired unit heaters
Hide thumbs Also See for PTC:
Table of Contents

Advertisement

sPeCIAl PreCAuTIons / sI (meTrIC) ConversIon fACTors
CAUTION
12. The minimum distance from combustible material is based
on the combustible material surface not exceeding 160°F.
Clearance from the top of the unit may be required to be
greater then the minimum specified if heat damage, other
than fire, may occur to materials above the unit heater at
the temperature described.
13. Allow 18" of clearance at rear (or 12" beyond end of
motor at rear of unit, whichever is greater) and access
side to provide ample air for proper operation of fan.
14. The concentric vent adapter box must be installed inside
of the structure or building. Do not install this box on the
exterior of a building or structure.
15. Purging of air from gas supply line should be performed
as described in the National Fuel Gas Code, ANSI Z223.1
(NFPA 54) - latest edition, or in Canada in CSA-B149
codes.
16. When leak testing the gas supply piping system, the
appliance and its combination gas control must be
isolated during any pressure testing in excess of 14" W.C.
(1/2 psi).
17. The unit should be isolated from the gas supply piping
system by closing its field installed manual shut-off valve.
This manual shut-off valve should be located within 6' of
the heater.
18. Turn off all gas before installing appliance.
19. Check the gas inlet pressure at the unit upstream of the
combination gas control. The inlet pressure should be
6-7" W.C. on natural gas or 12-14" W.C. on propane. If
inlet pressure is too high, install an additional pressure
regulator upstream of the combination gas control.
20. Service or repair of this equipment must be performed by
a qualified service agency.
21. Do not attempt to reuse any mechanical or electronic
ignition controller which has been wet. Replace defective
controller.
ImpORTANT
1. To prevent premature heat exchanger failure, do not locate
ANY gas-fired appliances in areas where corrosive vapors
(i.e. chlorinated, halogenated, or acidic) are present in the
atmosphere.
2. To prevent premature heat exchanger failure, the input to
the appliance as indicated on the serial plate, must not
exceed the rated input by more than 5%. Verify that the
blower has been set to the proper RPM for the
application. Refer to page 19 for blower adjustments.
3. Start-up and adjustment procedures must be performed
by a qualified service agency.

Before You BegIn

1. All literature shipped with this unit should be kept for future
use for servicing or service diagnostics. Leave manual with
the owner. Do not discard any literature shipped with this unit.
2. Consult piping, electrical, and venting instructions in this
manual before final installation.
3. Do not attach ductwork, air filters, or polytubes to any
propeller unit heater.
In the U.S., the installation of these units must comply with the
the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) - latest
edition, or in other applicable local building codes. In Canada,
the installation of these units must comply with local plumbing
or waste water codes and other applicable codes and with the
current code CSA-B149.1.
1. All installation and service of these units must be
performed by a qualified installation and service agency
only as defined in ANSI Z223.1 (NFPA 54) - latest edition or
in Canada by a licensed gas fitter.
2. This unit is certified with the controls furnished. For
replacements parts, please order according to the
replacement parts list on serial plate. Always know your
model and serial numbers. Modine reserves the right to
substitute other authorized controls as replacements.
3. Unit is balanced for correct performance. Do not alter fan
or operate motors at speeds below what is shown in this
manual.
4. Information on controls is supplied separately.

sI (metric) Conversion factors

To Convert
"W.C.
°F
BTU
Btu/ft
3
Btu/hr
CFH (ft
/hr)
3
CFH (ft
/hr)
3
CFM (ft
/min)
3
CFM (ft
/min)
3
feet
Gal/Hr.
Gal/Hr.
gallons
Horsepower
inches
pound
psig
psig
6-563.7
CAUTION
multiply By
0.249
(°F-32) x 5/9
1.06
37.3
0.000293
0.000472
0.00000787
0.0283
0.000472
0.305
0.00379
3.79
3.79
746
25.4
0.454
6.89
27.7
To obtain
kPa
°C
kJ
kJ/m
3
kW
m
/min
3
m
/s
3
m
/min
3
m
/s
3
m
m
/hr
3
l/hr
l
W
mm
kg
kPa
"W.C.
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents