Troubleshooting; Battery Checkout; Gate Not Operating - Chamberlain MSLDCBB Installation And Service Manual

1/2 hp commercial duty slide gate operator
Table of Contents

Advertisement

WARNING: Disconnect batteries and AC power before servicing
any mechanical or moving components.

BATTERY CHECKOUT

When the batteries become weak the gate will begin to run
noticeably slower. (NOTE: Batteries should only be checked when
you are sure they have had adequate time to fully charge.) Turn
off the AC power and run gate for 5 to 10 cycles while observing
low battery indicator LED D12. If LED 12 comes ON, batteries are
too weak to function properly. If LED 12 does not light, then
voltage should be checked as they still maybe near failure.
Correct voltage is approximately 25.5VDC. (NOTE: If LED D12
does light, gate will open to conserve batteries in this test or in a
real power loss, even if mode switch 8 on S2 is off.) Return of AC
power will clear low battery indicator. Correct charge voltage is
27.5 VDC with batteries not connected (Set with R63, shown on
the Control Board Layout page).
T R O U B L E S H O O T I N G

GATE NOT OPERATING

Is the HBEAT flashing?
Is the battery lo LED on?
Is S2-8 (open on AC fail) on?
Is the shadow input active?
Is the Safety, Backaway, or
Does the IRD light while
Is the IRD flashing?
Is the IRD on solid?
17
Gate will not operate.
Check the battery
No
connections.
Yes
Is the HBEAT
Yes
flashing now?
Is the AC power
No
Yes
Yes
No
Yes
No
Yes
Open input active?
No
Make sure the gate is not binding,
Yes
operating?
No
Yes
No
The run timer has expired.
Inspect the belt for slippage and
verify the fast run timer settings
are correct. Re-issue a command
to start the gate.
Yes
A double entrapment (E2)
condition has occurred
over 5 minutes ago. Clear
all the obstructions and
use the AUX input to reset
the gate.
Check fuse F4.
Replace if
blown.
No
Restore AC
power
and/or turn
No
AC power
LED on?
switch ON.
Is the AC power
LED on now?
No
Yes
Check fuse F3,
Allow unit to
Replace if blown.
charge before
operation.
Remove the active input to
allow the gate to open.
Remove the active input to
allow the gate to close.
then adjust the IRD. Verify the
gate reverses when obstructed.
Is the Entrapment
Alarm On?
No
Yes
The Edge input
(JP2) is active.
Clear obstruction
to restore
operation.
Is the Entrapment
Alarm On?
No
Yes
A double entrapment (E2)
condition has recently
occurred. Clear all
obstructions and use the
AUX input to reset the
alarm and gate.