The GE (General Electric) Digital Energy Match UPS, an uninterruptible power supply, protects your
equipment from all forms of power interference, including complete power failures.
1.2

Safety Rules

!
CAUTION:
RISK OF ELECTRICAL SHOCK. After installation, the UPS system (UPS +
battery pack) contains batteries. The appliance outlets may be electrically live, even when
the UPS is disconnected from the mains.
! The UPS contains potentially hazardous voltages. Do not open the UPS, there are no user
serviceable parts inside.
! All maintenance and service work, including replacement of the batteries, should be
performed by qualified service personnel.
1.3

Transport / Storage

! No liability can be accepted for any transport damage when the equipment is shipped in non-
original packaging.
! Store the UPS in a dry location with the batteries in a fully charged state. Storage temperature
must be within -20 +45 "C. If the unit is stored for a period exceeding 3 months, optimal battery
lifetime is obtained if the storage temperature does not exceed 25°C.
! If the unit is stored for an extended period of time, the batteries must be recharged periodically.
Connect the battery pack to the UPS. Subsequently connect the unit to a wall outlet and recharge
the batteries for 24 hours:
-
if the storage temperature is within -20 and +30°C: every 3 months,
-
if the storage temperature is within -20 and +45°C: every month.
The shipment contains a Match UPS, a battery pack, one mains power cord, two IEC male-female output
cords, a data cable, a CD ROM and this manual. After unpacking, inspect the UPS for damage. If any
damage is present please immediately notify the carrier and place of purchase.
IMPORTANT:
Before making any connection and switching on the UPS, please check the following conditions:
!
your mains supply is 220 - 240 Volts and 50 or 60 Hz, and
!
the total power demand of the connected equipment does not exceed the rated output power of
the UPS (indicated on the rating label) (7, fig. 1).
2.1

Installation Rules

! The UPS is intended to be used in normal domestic and office situations.
! Protect the UPS, according to the wiring rules, with a 16A D-type fuse.
! The UPS must be powered from a single phase grounded wall outlet. Do not use extension
cords.
! Avoid locations that are excessively humid, near water, near heat sources or in direct sunlight.
! The ambient temperature should not exceed 40"C. Optimal battery lifetime is obtained if the
ambient temperature does not exceed 30"C.
! If you stack the UPS and its battery pack, always place the UPS on top.
! It is important that ventilation air can move freely around and through the unit. Do not block the air
vents.
! Do not plug appliances such as electric heaters, toasters and vacuum cleaners into the UPS.
! Be careful when connecting laser printers: be sure that the demanded power does not exceed the
capacity of the UPS.
! The sum of the leakage currents of the UPS and the connected loads should not exceed 3.5mA.
LX: OPM_MAE_XXX_2K2_3K0_XGB_V020
1 - Introduction

2 - Installation