Apart from the options described in 4.2 and 4.3 the following options are possible:
5.1

Extended Runtime

Extended runtime can be obtained by connecting more than one battery pack to the UPS (see 2.2.1). In
this case, to allow a reliable recalculation of the available runtime, the UPS must be informed about the
new total battery capacity. You can reprogram the battery capacity through the RS232 port, using the UPS
configuration tool that came with the unit (CD ROM, see 6.3). Simultaneously the recharge current will be
increased. Please note that if the UPS is not connected to the mains, and the battery pack is
disconnected from the UPS, the unit will return to the default settings.
Dependent of the charge condition of the new batteries the new runtime calculations may temporarily be
unreliable.
For extended runtime at 25
maximum load must be derated to 1.85kVA (Match 2200) and 2.5kVA (Match 3000).
5.2

PowerFLAG SerVICe Box for Modem Connection

If you connect the PowerFLAG SerVICe Box between the communication port of the UPS and a modem,
a programmed number can be dialed in case of a UPS alarm. It also allows service personnel to dial in
and check the status of the UPS to perform remote diagnostics. This way service costs, specially in
remote areas, can be reduced considerably.
6.1

General

The GE Digital Energy Match UPS is virtually maintenance free: take care of proper environmental
conditions and keep air inlets-outlets free of dust.
Please read 2.1.
6.2

Batteries

The service life of the battery is up to 6 years, depending on operating conditions.
As a healthy battery is critical to the performance of the UPS, an automatic battery test is performed
regularly to ensure failsafe operation. Moreover, keypad 'I' allows a manually started battery test.
See 3.2.4.
When the condition of the battery is critical, a 'replace battery' alarm will be activated. Have your dealer
replace the batteries as soon as possible. See 3.3.6.
6.3

UPS Configuration Tool

With the UPS configuration software, that came with the unit on CD ROM, you are able to change the
setting of the 'auto-off' function (3.2.3) and reprogram the battery capacity (5.1).
Insert the CD ROM in your computer, and
1.
Select RUN from the start menu
2.
Type a:\conftool (type for 'a' the appropriate drive letter)
3.
Press ENTER
See also a:\README.TXT.
LX: OPM_MAE_XXX_2K2_3K0_XGB_V020

5 - Optional Features

C ambient temperature no derating is required. For extended runtime at 35
°

6 - Maintenance

8
GE Digital Energy
GE DE Match 2200-3000: user manual 2.0 (GB)
C,
°