Gas Settings; Chimney Sweep' Mode - Baxi MainEco Heat 15 Installation And Service Manual

Gas fired wall mounted powered flue condensing boiler
Hide thumbs Also See for MainEco Heat 15:
Table of Contents

Advertisement

7.4

Gas Settings

Flue Sampling
Point
Plug
Analyser Probe
After refitting the sampling point
plug ensure there is no leakage
of products !
7215845 - 01 (08/14)
7.4.1
1. The current operating condition of the boiler is shown by the
button can flash in a range of colours and at different
frequencies.
2. Follow the flow chart on the next page to comply with the
requirement to check combustion on commissioning.
3. Setting the boiler to maximum and minimum heat outputs is
achieved as follows;
Fig. 33
'Chimney Sweep' Mode (CSM)
button on the User Interaction Controller. The
Press the
button for 3 seconds.
CSM is activated and will go to the min rate.
Pressing again will make it adjust to max rate.
To exit press the RESET for 3 seconds.
Commissioning
7
MainEco Heat
41