Camus Hydronics MFH060 Installation, Operation And Service Manual page 52

Modulating micoflame series gas fired residential and commercial copper tube boilers
Table of Contents

Advertisement

MF 400 – 600
To adjust the high fire setting
Set the Target Temperature to 190
Once the appliance is at maximum fan speed locate the input adjustment screw on the top side of the gas
valve. Using a flat head screwdriver turn the screw clockwise to decrease CO
clockwise to increase CO
of the adjustments. After adjusting the screw wait a moment for the combustion levels to stabilize before
attempting to make any further adjustments. Continue this procedure until combustion levels are satisfied.
Reset the Target Temperature to normal operating conditions on the BTC 1 Controller.
To adjust the low fire setting
Observe the Boiler Inlet Temperature. Set the Boiler Target temperature so that it is 10
Inlet Temperature. The boiler will begin to modulate to low-fire as setpoint is being reached. The actual
modulation rate can be shown on the screen as Modulation, this will be shown as a percentage. Low-fire
is achieved at 25%.
The MicoFlame will respond immediately and operate at low fire. When this is achieved locate the low fire
adjustment screw as illustrated in Figure 28. Using a flat screwdriver rotate clockwise to increase CO
levels and counter-clockwise to decrease CO
replace the screw cap back on to the gas valve.
Reset the Target Temperature to normal operating conditions on the BTC 1 Controller.
Figure 29: MF 400 – 600 Gas Valve
o
F using the BTC 1 Controller.
levels. Turn the screw 1/4 turn in either way for each adjustment to keep track
2
Table 12: Combustion Values
Max.
Non-
Fire
Condensing
Min.
Fire
Max.
Fire
Condensing
Min.
Fire
levels. When the correct combustion values are achieved
2
Natural Gas
CO
CO
CO
2
7.5% -
< 50
9.0% -
8.5%
PPM
10.0%
7.0% -
< 50
8.5% -
7.5%
PPM
9.0%
8.5% -
< 50
10.0% -
9.0%
PPM
10.5%
7.5% -
< 50
9.0% -
8.0%
PPM
9.5%
48
levels and counter-
2
o
F above the Boiler
Propane
CO
2
< 50
PPM
< 50
PPM
< 50
PPM
< 50
PPM
2