MODE 8: EXTERNAL DRIVE OPEATION: VIEW DISPLAY

From the Home display;
1) Press [ITEM] to view the following parameters:
Display
Parameter
Parameter Description
Name
Boiler Outlet
Real-time Outlet Temperature to
Temperature
Boiler
Boiler Inlet
Real-time Inlet Temperature to
Temperature
Boiler
Real-time temperature difference
Boiler Delta
between the outlet sensor and the
T
inlet sensor.
Real-time modulating output
Modulation
percentage
Monitors the amount of
operational time since the
MicoFlame was installed. The first
Total Run
two digits are the number of
thousands of hours and the three
Time Since
digit display shows the number of
Installation
hundreds of hours.
Press
reset the counter
38
simultaneously to
Parameter Range
o
14 to 266
F
o
(-10 to 130
C)
o
14 to 266
F
o
(-10 to 130
C)
o
-99 to 252
F
o
(-72 to 122
C)
0 to 100%
Alternates
between 00 and
999