Confirm that the online values of
DN00_STA_IN[5] and
DN00_STA_IN[6] are True.
*DN00_STA_IN[5]: CFN
0: Follow the setting of
parameter A002.
1: DeviceNet reference
*DN00_STA_IN[6]: RFN
0: Follow the setting of
parameter A001.
1: DeviceNet reference
6
Enter 100 in the Modify Column of
DN00_DATA_OUT.
*[DN00_DATA_OUT: Rotation
Speed Reference]
The unit of the rotation speed is
0.01 Hz.
After entering values, press the
Enter key on the keyboard. The
online value is changed to 100.
7
Confirm that RUN LED indicator of
the Inverter is not lit and
shown on the data display (Output
frequency setting).
8
Click True in the Modify Column of
DN00_CMD_OUT[0].
*DN00_CMD_OUT[0]: FW
0: Stop/1: Forward
The online value changes to True.
0.00
is
7.Connection Procedure