VisionPRO
®
IAQ
Installer system test
During installer setup, press ▼
repeatedly until "Test" appears
0120
DONE
System test
1
Cooling system
2
Fan system
3
Heating system
4
Emergency
heating system
5
Humidifier
6
Dehumidifier
7
Ventilator
Other messages
P
Ventilation meets ASHRAE 62.2 standard (Function 0404)
F
Ventilation does not meet ASHRAE 62.2 standard (Function 0404)
Err
See error codes (page 22)
CAUTION: EQUIPMENT DAMAGE HAZARD. Compressor protection is bypassed
during testing. To prevent equipment damage, avoid cycling the compressor quickly.
(English: Page 4 • Français: Page 10 • Español: Página 16)
20
System status
0 Off
1 Test cooling stage 1
2 Test cooling stages 1 & 2
0 Fan off
1 Fan on
0 Off
1 Test heating stage 1
2 Test heating stages 1, 2
3 Test heating stages 1, 2, 3
4 Test heating stages 1, 2, 3, 4
0 Off
1 Test EmHeat stage 1
2 Test EmHeat stages 1, 2
0 Off
1 On
0 Off
1 On
0 Off
1 On
Test
number
TEST
DONE
Press ▲▼ to
select test
Press DONE to terminate testing
9
System
status
1
0
Press ▲▼ to
change status