Panasonic WH-SDF09C3E8 Service Manual page 97

Air to water heat pump
Hide thumbs Also See for WH-SDF09C3E8:
Table of Contents

Advertisement

16.5.27 Outdoor Discharge Pipe Temperature Sensor Abnormality (F40)
Malfunction Decision Conditions:
During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe
temperature sensor are used to determine sensor error.
Malfunction Caused:
1
Faulty connector connection.
2
Faulty sensor.
3
Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue for 5 seconds.
97

Hide quick links:

Advertisement

Table of Contents
loading