Panasonic WH-SDF09C3E8 Service Manual page 88

Air to water heat pump
Hide thumbs Also See for WH-SDF09C3E8:
Table of Contents

Advertisement

16.5.18 Input Over Current Detection (F16)
Malfunction Decision Conditions:
During operation of cooling and heating, when outdoor current above 10.6A is detected by the current
transformer (CT) in the outdoor unit PCB.
Malfunction Caused:
1
Excessive refrigerant.
2
Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue 3 times in 20 minutes.
88

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents