12.1.5 Setting Water Outlet Temperature for Heat Mode
The set temperature define the parameters for the outdoor ambient temperature dependent operation of the unit.
Where by the internal water setting temperature is determined automatically depending on the outdoor
temperature. The colder outdoor temperatures will result in warmer water and vice versa. The user has the
possibility to shift up or down the target water temperature by control panel setting.
Change in setting water outlet temperature is updated every 30 minutes.
12.1.5.1
Heating Mode Operation Time Chart
1
3 ways valve control:
3 ways valve switch and fix to heating side.
o
2
Heatpump operate follow normal heating operation.
3
Backup heater operate follow normal operation.
4
Solar 3 way valve operates follow solar operation specification.
12.1.6 Water Temperature Thermo Shift Setting
Switchs are ignored during "PUMPDW" = ON.
Switchs are ignored during "STATUS" = ON.
"
", "
", "SELECT" switch are ignored if "SETTING" = OFF.
"CANCEL" switch is ignored if "SETTING" = OFF & "STATUS" = OFF.
Example