ii. Case 2
- Heatpump THERMO OFF TEMP:
1
Heatpump THERMO OFF TEMP = 55°C + [+2°C].
2
Water outlet temperature > Heatpump THERMO OFF TEMP for continuous 3 minutes, heatpump OFF but
water pump ON.
- Heatpump THERMO ON TEMP:
1
Heatpump THERMO ON TEMP = Water inlet during thermo off time + [-3°C].
2
Heatpump ON back when water outlet temperature < Heatpump THERMO ON TEMP.
iii. Case 3
- Heatpump THERMO OFF TEMP:
1
Water inlet temperature > 52°C for continuous 60 sec, heatpump OFF and water pump OFF.
- Heatpump THERMO ON TEMP:
1
Heatpump THERMO ON TEMP = Water inlet during thermo off time + [-3°C].
2
Water pump ON back when tank temp. < Tank temp. when heatpump thermo off + [-3°C].
3
Heatpump only ON back after water outlet temperature < Heatpump THERMO ON TEMP & water pump ON
for 3 minutes.
Booster heater control
- Booster heater turn On and Off follow normal operation.
- Booster heater turn ON condition:
1
During startup time (initialization), Booster heater turn ON after DELAY TIMER.
2
When tank temperature lower than HEATER ON TEMP
3
20 minutes from previous heater off.
- Booster heater turn OFF condition:
1
When tank temperature higher than tank set temperature for continous 15 sec.
Solar 3 way valve
- Solar pump operates follow solar operation specification.
Others
- Indoor backup heater cannot be ON during tank mode only.