Recircula on Mode (RL94 Models)
The Rinnai water heater has the ability to control a 
recircula on pump.  Two modes are available, 
Economy and Comfort, which recirculate the water in 
the plumbing system to provide hot water more 
quickly when a tap is opened.   
Recircula on mode is for residen al installa ons only.  
Recircula on mode cannot be used with the Bath Fill 
controller (BC‐100V), an air handler, or with mul ple 
Rinnai water heaters. 
The maximum Rinnai temperature se ng while in 
recircula on mode is 140°F (60°C). 
Pump Requirements 
Voltage: 
120V, 60 Hz 
Amperage:  less than 2 amps 
NOTE:  The Rinnai PC board will be damaged if 
amperage exceeds 2 Amps. 
Check valve:  An integral flow check (IFC) valve is 
required.  See plumbing diagram. 
Pump Size 
The pump should be sized for 2.5 GPM at the pressure 
loss through the tankless water heater and the supply 
and return plumbing in the recircula on loop. 
For more informa on on sizing the pump refer to the 
sec on "Pump Sizing for Circula on" in the Rinnai Hot 
Water System Design Manual. 
Installa on 
1.  Turn off the electrical power supply by unplugging 
the power cord or by turning off the electricity at 
the circuit breaker.   
2. Install the recircula on pump on the return line 
according to the pump manufacturer installa on 
instruc ons.  Install a check valve in the return 
line as shown in the Plumbing Diagram if one is 
not integrated into the pump.
3. The wire harness for the recircula on pump is 
bundled with the wire harness from the PC board.  
The connector has a black and white wire with the 
label "Cut wire to connect to pump".  To connect 
to the pump, cut the connector, splice the wires, 
and add 4 Amp fuse to the hot wire (black) of the 
pump.  Connect the ground wire from the pump 
to a screw at the base of the water cabinet .  
Refer to the Pump Electrical Connec on Diagram.  
Follow Electrical Code and pump manufacturers 
recommenda ons. 
 
 
4.  Adjust the dip switch by moving the 4th switch in 
the whie set of switches (SW2) to ON. 
For Economy mode, set the 8th switch in the 
white set of switches (SW2) to OFF (default). 
For Comfort mode, set the 8th switch in the white 
set of switches (SW2) to ON. 
Economy Mode 
Comfort Mode 
5.  Connect power to the water heater.  Press the 
Power bu on on the controller.  The pump and 
water heater will turn on to raise the recircula on 
loop temperature. 
HOT WATER
SUPPLY LINE
RECIRCULATION
LOOP
HOT WATER OUTLETS
NOTE:  DO NOT install the Rinnai Scale Control system 
within the recircula on loop.   
PUMP
VC Series Manual 
Se ngs for SW2  
 
(bank of white switches)  
 
Switch 4 
ON 
ON 
COLD WATER SUPPLY LINE
ELECTRICAL
THERMAL
CONNECTION
EXPANSION TANK
(POWER)
CHECK VALVE
(REQUIRED)
PUMP
Plumbing Diagram 
Cut connector 
and splice wires. 
4 Amp 
Fuse 
BL 
Pump Electrical Connec on 
Switch 8 
OFF 
ON 
CHECK
VALVE
RINNAI
SCALE
CONTROL
(RECOMMENDED)
PC 
Board 
29 