Wiring - Secutron MR-2900 Installation Manual

Fire alarm control unit
Hide thumbs Also See for MR-2900:
Table of Contents

Advertisement

2.4 Wiring

Power Connections
The Main Control Unit requires an AC power supply. See Figures 5 and 6 below.
The batteries forming the Battery Pack are wired in series. The Battery Pack attaches to the two wires
coming from the Power Supply Board, the black wire to the black (negative) terminal and the red wire to
the red (positive) terminal. The internal batteries are not used when an external battery box is used. The
wires for connecting the power supply board to the batteries are supplied with the panel if a battery box is
ordered at the same time.
Figure 5: 120VAC Power Connection
Warning: Never connect or disconnect the batteries while the AC power is off.
Conventional Style B (Class B) Circuit
Figure 7: Conventional Style B (Class B) Wiring
Note: 2-wire smoke detectors cannot be used on this type of circuit. This circuit may be wired on any of
the 24 input circuits on the MR-2900 terminal boards.
12
Figure 6: 240VAC Power Connection
This is a 2-wire power-limited and supervised Style
B
(Class
EOL-471
conventional normally open contact devices and an
end-of-line resistor, supported by the MR-2928
smoke and contact module. Maximum wire lengths
are shown in Table 2. The end-of-line resistor is a
Ω
470
resistor EOL-471. Devices and the end-of-
line resistor are connected as illustrated in Figure 7.
B)
initiating
device
circuit
using