Secutron MR-2900 Installation Manual page 28

Fire alarm control unit
Hide thumbs Also See for MR-2900:
Table of Contents

Advertisement

Annunciator, UDACT and Reverse Polarity Wiring
Figure 28: MR-2614, MR-2644, MR-2900-
DACT and MR-2900-CITY Wiring
Evax System Wiring
MR2900 BACKPLATE
MR2925 OR MR2926
TERMINAL BOARD
COMLINK 3
Figure 29: EVAX System Wiring
**The MR-2900 panel requires the use of the MR-2109-4 board.
Notes:
• For all EVAX installations, the maximum wiring distance from the FACP to the HMX panel is 20
feet in conduit. The two panels must be in the same room.
• MV-2700M and MV-2700D are not ULC listed.
• MV-2700M must be connected to an MV-2700D. The MV-2700M (M = Master) generates the
audio signals. The MV-2700D (D = Distributed) distributes the audio signal via NACs.
• For information on connecting an MV-2700M to an MV-2700D, refer to those modules installation
instructions.
• Devices connected to COMLINK 3 are to be installed close nippled.
22
CONDUIT
20' MAX
TX
RX
GND
TB9
The MR-2614 and MR-2644 Annunciators, the MR-
2900-CITY Reverse Polarity module and the MR-
2900-DACT Dialer are connected to COMLINK 3 of
the panel by 4 wires; 2 for power and 2 for
communications. The communications wiring is
polarity sensitive. An example of the wiring is shown
in Figure 28. Up to eight of each type of annunciator
and either one dialer or one reverse polarity module
can be connected to the MR-2900. If more than one
MR-2614 is used, the 3.9k
2614 terminals should be removed from all but the
last MR-2614. The MR-2900 panel requires that the
MR-2109-3 communications board be installed. The
maximum length of communications wiring is 900m
(3000 ft) using 22 AWG. The maximum length of
power wiring is 300m (1000 ft) using 18 AWG.
MV 2700 M
TX
TS3
RX
GND
Ω
resistor across the MR-