Hitachi SJ100DN DeviceNet Series Instruction Manual page 43

Hide thumbs Also See for SJ100DN DeviceNet Series:
Table of Contents

Advertisement

42
Network Control and Monitoring
DeviceNet networks support three baud rates, listed in the following table.
Baud Rate
125 kbps
250 kbps
500 kbps
NOTE: If thin cable is used for the trunk line, the maximum distance is 100m (for all
baud rates).
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Trunk length
(thick cable)
Maximum
500m (1640 ft.)
6m (20 ft.)
250m (820 ft.)
6m (20 ft.)
100m (328 ft.)
6m (20 ft.)
Drop Length
Cumulative
156m (512 ft.)
78m (256 ft.)
39m (128 ft.)