4.2.3 Live zero and setpoint input range

S1.6
S1.7
OFF
OFF
OFF
OFF
OFF*
ON*
ON
OFF
ON
OFF
ON
ON
* Default setting
The analog input can be adapted to the various process controllers
with the setpoint and live zero switches. The following signal ranges
can be set:
0(4)-20mA (R
(R
= approx. 88k ).
i
+5V supply voltage can be taken from terminal X2.8 for a setpoint
potentiometer (5k
4.2.4 Analog output
(only with ...H RL1 and ...H RLP1)
The analog output allows the effective values U
to be displayed. The output signal level can be set.
Analog output
S1.9
OFF*
ON
OFF
ON
* Default setting
S1.8
Signal level
OFF
ON
ON*
OFF
ON
ON
= approx. 250 ), 0-5V (R
i
< R
< 10kΩ)
Poti
S1.10
ON*
ON
OFF
OFF
0-10V
0-5V
44k
0-20mA
2-10V
1-5V
44k
4-20mA
= approx. 44k ), 0-10V
i
load
Output level
0 - 10V
2 - 10V
0 - 20mA
4 - 20mA
43
Input resistance
88k
(e.g. for setpoint
potentiometer)
250
88k
(e.g. for setpoint
potentiometer)
250
, I
or P (H RLP)
load
EN