5. Installation

DANGER
Dangers during Installation
Risk of injury / Risk of damage to the device or plant
> Observe all safety regulations in the safety chapter
DANGER
Unsafe system due to incorrect installation
The plant cannot be operated safely and poses a threat
to persons.
> Only install the device in an upright position.
> Ensure sufficient ventilation of the cabinet if mounted
in a cabinet.
> Observe minimum spacing (Clearance: 150 mm above,
100 mm below). The devices can be installed next to
each other without spacing between.
> Ensure that the device cannot be heated up by heat
sources below it. (The power loss is given in the type
overview table , see page 87, Technical data)
> Ground the device in accordance with local regulations.
(grounding screw / nut for protective conductor connec-
tion to fixing adapter). Grounding also serves for EMC
means (Y capacitor 4.7 nF).
CAUTION
Use of incorrect connection cables
Incorrect connection cables can lead to malfunctions.
Use shielded control conductors to connect the control
signals.
For use in UL conditions: Only use 60°C or 75°C
copper conductors for power connections (as indicated in
Technical Data).
58