AEG Thyro-A Operating Instructions Manual page 59

Thyristor power controller
Hide thumbs Also See for Thyro-A:
Table of Contents

Advertisement

NOTE
Connecting the control signals
The following control signals are necessary for operating
the devices:
- Setpoint (terminal X2.4 or via bus option)
- Pulse inhibition (to ground, on terminal X2.1, X2.2;
bridge present)
If the pulse inhibition bridge is not connected, the device
is blocked and is not operating. Communication is still
possible via the interface (see page 63, Connecting pulse
inhibition).
The device is parameterised when delivered and also adapted to the
particular power unit.
Default setting:
• Operating mode VAR (S1.1 and S1.2)
• Transformer load R201 90°el. / 60°el. (depending on the type of
device)
Other default settings are listed in the chapter Operation and Settings
(DIP switches (see page 39, DIP switch S1) and potentiometers (see
page 44, Potentiometer).
> Check default settings and adjust to application conditions if neces-
sary (e.g. operating mode, control mode, restrictions, monitoring,
analog output, fault messages etc.)
The devices can be installed next to each other without spacing
between.
Observe minimum spacing (free space: 150 mm above, 100 mm
below).