Adapting Analog Output (Scale) (Only For - AEG Thyro-A Operating Instructions Manual

Thyristor power controller
Hide thumbs Also See for Thyro-A:
Table of Contents

Advertisement

4.3.6 Adapting analog output (scale) (only for ...H RL1 and ...H RLP1)
The scale of the analog output is adapted with potentiometer R204
SCALE OUTPUT, if, for example, the scale of the display does not cor-
respond to the nominal data (see page 41, Analog output).
Tab. 6a Analog output (scale) Thyro-A 1A, 2A
Setting
(default = 0-20mA,
corresponds to type value 2A (H, HRL1, HRLP1) at
(current/voltage/power)
Potentiometer turns
(from left stop)
Setting aid, analog output
(Switch S1.10 = „OFF")
Setting aid, analog output
(Switch S1.10 = „ON")
Tab. 6b Analog output (scale) Thyro-A 3 A
Setting
(default = 0-20mA,
corresponds to type value/
(current/voltage/power)
Potentiometer turns
(from left stop)
Setting aid, analog output
(Switch S1.10 = „OFF")
Setting aid, analog ouput
in volts
(Switch S1.10 = „ON")
Analog output: X2.9 (+); X2.5 (ground) *1 only with ...H RLP1
Example adaptation at the analog output
Thyro-A 3A 400-30 H RLP1 (U
Measuring instrument for 4-20 mA with scale 20 kW
Setting R204:
Setting aid in mA:
Setting aid in V:
1A (H, HRL1, HRLP1) at
in mA
in mA
in mA
6.24 * (20,7kW/20kW)
6.93mA * (20,7kW/20kW)
3.46V * (20,7kW/20kW)
U-, I-, P display -
U-, I-display
Potentiometer R204
SCALE OUTPUT
4 turns * (type value power
controller / scale end value)
4mA * (type value power
controller / scale end value)
2V * (type value power
controller / scale end value)
3A (H, HRL1) at
U-, I display
Potentiometer R204
SCALE OUTPUT
3.6 turns * (type value power
controller/scale end value)
4mA * (type value power
controller/scale end value)
2V * (type value power
controller/scale end value)
= 400V, I
= 30A, P
type
type
50
2A (HRLP1) at
P display
Potentiometer R204
SCALE OUTPUT
4.62 turns * (P
type power controller
scale end value)
4.62mA * (P
type power controller
scale end value)
2.13V * (P
type power controller
scale end value)
3A (HRLP1) at
P display*
1
Potentiometer R204
SCALE OUTPUT
6.24 turns * (P
type power controller
scale end value)
6.93mA * (P
type power controller
scale end value)
3.46V * (P
type power controller
scale end value)
= 20.7kW)
type
Setting aid
6.5 turns
(from left stop)
7.17mA
3.58V
/
/
/
/
/
/