Fault Signalling Relay K1 - AEG Thyro-A Operating Instructions Manual

Thyristor power controller
Hide thumbs Also See for Thyro-A:
Table of Contents

Advertisement

If the power controller is supplied from an external 24V source at the
extra electronics supply input (see page 62, Connecting additional
electronics supply), the device sends a frequency error message but
does not switch off.

3.8.2 Fault signalling relay K1

(only for ...H RL1 and ...H RLP1)
Fault signalling relay K1 has a changeover contact. Messages that
cause the fault signalling relay to switch can be set with THYRO-
TOOL FAMILY. In the default state, fault signalling relay K1 functions
on the closed circuit principle.
In the event of the following errors, the fault signalling relay de-ener-
gizes and the power controller switches off:
• SYNC error
• internal error
• undervoltage in the mains
• master/Slave error
• error rotating field / phase
In the event of the following errors, the fault signalling relay de-energizes,
the power controller remains on and a message is sent (LED):
• excess temperature
• undercurrent in the load circuit
NOTE
Default setting
The function explained here is described in the default
state.
This setting can be changed with a bus module or with
THYRO-TOOL FAMILY.
X3.1 root
X3.2 N/O contact
X3.3 N/C contact
31
EN