Sanyo SHA TM64 AGB Instruction Manual page 24

Control system for spw air conditioner system
Table of Contents

Advertisement

Schedule Timer
Creating Timer Groups
The schedule timer can be set for 6 time status changes.
These can be used to create up to 8 groups (timer groups).
For systems in which schedule timers are used, set the timer
groups to match the central control addresses of the indoor
units that will be subject to group timer control.
The timer-group settings for the schedule timer involve as-
signment of central control addresses. Therefore, use the
system controller (or other central control device) or wired
remote controllers to set the central control addresses of the
indoor units, then make the schedule timer settings.
Procedure for making fi xed timer group settings (fi xed groups)
(1) First, use a different central control device (system controller or other device) or the wired remote controllers to set the cen-
tral control addresses, as assigned in the fi gure above, to the indoor units that will be subject tom group timer control.
(2) Next, use S41 switches 2 and 3 to set the number of timer groups you wish to create.
(3) Finally, turn ON the schedule timer power. Initial communications are performed. (SCAn blinks in the display.) The normal
display appears after several minutes, and the timer group settings are confi rmed.
Procedure for making manual timer group settings (manual group assignments)
Manual timer group settings allow central control addresses to be assigned freely within the timer groups.
(1) Turn ON S41 setting switches 2 and 3, then turn ON the power. Restart and initial communications are performed. (SCAn
blinks in the display.) The normal display appears after several minutes.
(2) When the normal display appears, press and hold the schedule timer
button for 4 seconds or longer. "Ad-01" appears, blinking, in the current time display. (Ad indicates "address" and 01 is the
central address number.)
(3) Use the
button in the
control address to assign and register for that timer group. Press the
address.
area to select the timer group. Then use the
[Setting fixed timer groups]
Schedule timer
Central control address 1 – 64
2
8
1
Central control address 1 – 8
Central control address 1 – 16
17
18
24
Central control address 17 – 24
Central control address 17 – 32
33
34
40
Central control address 33 – 40
Central control address 33 – 48
49
50
56
Central control address 49 – 56
Central control address 49 – 64
button, the timer
button in the
button to register the selected central control
1 fixed timer group (64 units together)
4 fixed timer group (16 units together)
8 fixed timer group (8 units together)
9
10
16
Central control address 9 – 16
25
26
32
Central control address 25 – 32
41
42
48
Central control address 41 – 48
57
58
64
Central control address 57 – 64
button, and the
area to select the central
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents