Viessmann VITODENS 200-W Technical Data Manual page 36

Gas-fired wall-mounted condensing boiler 12 to 285 mbh (3.5 to 83.5 kw) multi-boiler installation 480 to 2280 mbh for models 45, 60 and 80
Table of Contents

Advertisement

Accessories
Accessories for Vitodens 200-W
Low-Loss Header (continued)
Low-loss header design (Type 80/50 or 120/80)
Principle of Operation
36
Vitodens 200-W, B2HA 19 to 80 Technical Data
IMPORTANT
Use only a Viessmann supplied temperature sensor.
Do not use any other manufacturer's temperature sensor.
Legend
AB
Air Bleed
BR
Boiler Return
BS
Boiler Supply
BY
Bypass (with laminar flow)
D
Debris and/or air
DV
Drain Valve
SC
Sensor Cable
SR
System Return
SS
System Supply
TS
Viessmann Temperature Sensor
SW
Sensor Well
IMPORTANT
When installing a low-loss header, the system mixed
supply temperature (T3) must be calculated as follows:
Legend
T1
Boiler supply temperature
T2
Boiler return temperature
T3
System supply temperature
T4
System return temperature
Vprimary
Boiler circuit flow rate
Vsecondary
Heating circuit flow rate
Vbypass
Bypass flow rate
Qprimary
Heat supplied by boiler
Qsecondary
Heat consumed by system
Vprimary < Vsecondary
T1 > T3
T2 = T4
Qprimary = Qsecondary
T1 167° F (75° C)
Vsecondary=Vprimary+Vbypass
Model No.
Type 80/60
Type 120/80
Type 160/80 *1
Type 200/120 *1
*1 Floor-mounted version (typically used for
multiple-boiler installations).
Max. system flow rate
19.5 GPM (4.4 m
3
/h)
35.2 GPM (8 m
3
/h)
44 GPM (10 m
3
/h)
80 GPM (18 m
3
/h)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents