Indoor Unit - Daikin RXMQ4·5·6PVE Service Manual

R-410a heat pump 50/60hz cooling only
Table of Contents

Advertisement

Si34-603
1.2

Indoor Unit

FXCQ, FXFQ, FXKQ, FXSQ, FXMQ, FXHQ, FXAQ, FXLQ, FXNQ
(3)
Filter
Code
Appendix
Heat exchanger
Fan
(2)
(1)
Electronic
Filter
expansion valve
Name
(1)
Electronic expansion valve
Suction air temperature
(2)
thermistor
(3)
Liquid pipe
(4)
Gas pipe
Capacity
20 / 25 / 32 / 40 / 50M(A)
63 / 80 / 100 / 125M(A)
(4)
Code
Used for gas superheated degree control while in
Y1E
cooling operation or subcooled degree control while
in heating operation.
R1T
Used for thermostat control.
Used for gas superheated degree control while in
R2T
cooling operation or subcooled degree control while
in heating operation.
Used for gas superheated degree control while in
R3T
cooling operation.
(mm)
GAS
Liquid
φ12.7
φ6.4
φ15.9
φ9.5
Piping Diagrams
Gas piping connection port
Flare connection : φ15.9 or less
Attached piping : Above φ19.1
Liquid piping connection port
(Flare connection)
DU220-602J
Main function
207