E9" Outdoor Unit: Malfunction Of Moving Part Of; Electronic Expansion Valve (Y1E, Y3E) - Daikin RXMQ4·5·6PVE Service Manual

R-410a heat pump 50/60hz cooling only
Table of Contents

Advertisement

Si34-603
3.19 " E9 " Outdoor Unit:

Electronic Expansion Valve (Y1E, Y3E)

E9
Remote
Controller
Display
Applicable
RX(Y)MQ4~6P
Models
Method of
Check disconnection of connector
Check continuity of expansion valve coil
Malfunction
Detection
Malfunction
Error is generated under no common power supply when the power is on.
Decision
Conditions
Supposed
Causes
Troubleshooting
Malfunction of Moving Part of
Defect of moving part of electronic expansion valve
Defect of outdoor unit PC board (A1P)
Defect of connecting cable
Troubleshooting by Indication on the Remote Controller