Daikin RXM-M9 Technical Data Manual
Hide thumbs Also See for RXM-M9:

Advertisement

Split
Air Conditioning
Technical Data
RXM-M9

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RXM-M9 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Daikin RXM-M9

  • Page 1 Split Air Conditioning Technical Data RXM-M9...
  • Page 3: Table Of Contents

    ........... 35 • Split - Sky Air • RXM-M9...
  • Page 4: Features

    • Anti-corrosion treated outdoor heat exchanger fin • Daikin outdoor units are neat, sturdy and can easily be mounted on a roof or terrace or simply placed against an outside wall Outdoor unit silent operation...
  • Page 5: Specifications

    Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. • Split - Sky Air • RXM-M9...
  • Page 6: Capacity And Power Input

    8,530 11,943 17,061 kcal/h 2,150 3,009 4,299 Heating capacity Nom. 3.40 4.50 5.80 Btu/h 11,601 15,355 19,790 kcal/h 2,923 3,869 4,987 Power input Cooling Nom. 0.60 1.09 1.55 Heating Nom. 0.77 1.19 1.60 • Split - Sky Air • RXM-M9...
  • Page 7: Capacity And Power Input

    2.31 3.10 3.84 3.96 SCOP/A 4.24 4.10 3.90 4.04 Annual energy 1,058 1,377 1,372 consumption Eurovent Sound power level Cooling Nom. outdoor Sound power level Cooling Nom. indoor Piping length Cooling Measur conditio • Split - Sky Air • RXM-M9...
  • Page 8: Capacity And Power Input

    Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. 2-6 Capacity and Power input FCAG35A/RXM35M9 FCAG50A/RXM50M9 FCAG60A/RXM60M9 Indoor unit FCAG35AVEB FCAG50AVEB FCAG60AVEB Outdoor unit RXM35M3V1B9 RXM50M3V1B9 RXM60M3V1B9 • Split - Sky Air • RXM-M9...
  • Page 9: Capacity And Power Input

    11,601 17,061 19,449 kcal/h 2,923 4,299 4,901 Heating capacity Nom. 4.00 6.00 7.20 Btu/h 13,649 20,473 24,567 kcal/h 3,439 5,159 6,191 Power input Cooling Nom. 0.91 1.56 1.73 Heating Nom. 0.98 1.79 2.17 • Split - Sky Air • RXM-M9...
  • Page 10: Technical Specifications

    1.80 Stages Quantity Passes Quantity Tube type ø7 Hi-XD ø8 Hi-XA Type Waffle fin (PE) Compressor Model 1YC25GXD#C 2YC40JXD#C Oil Amount cm³ Type Hermetically sealed swing compressor Output 800.0 1,300 Oil Type FW68DA • Split - Sky Air • RXM-M9...
  • Page 11: Electrical Specifications

    For power supply Quantity Remark Earth wire included For connection with indoor Quantity Remark Earth wire included Notes Contains fluorinated greenhouse gases See separate drawing for operation range See separate drawing for electrical data • Split - Sky Air • RXM-M9...
  • Page 12: Electrical Data

    &E ZyD D s  dyD D s  ZyD D s  dyD D s  Z>   Z>    t K&D &> & > & /&D D& & • Split - Sky Air • RXM-M9...
  • Page 13 &yD & s  ZyD D s  &E ZyD D s  dyD D s  Z>   D& &    t Z> K&D /&D & > &> & • Split - Sky Air • RXM-M9...
  • Page 14: Capacity Tables

    FDXM25F3 / ZyD D &Z &   d ^, W/ d ^, W/ d ^, W/ d ^, W/ d ^, W/ d ^, W/ &Z  t &Z &  t   > • Split - Sky Air • RXM-M9...
  • Page 15 ZyD D   &Z & d ^, W/ d ^, W/ d ^, W/ d ^, W/ d ^, W/ d ^, W/  t &Z &Z &  t   > • Split - Sky Air • RXM-M9...
  • Page 16 & ZyD D &Z &   d ^, d ^, d ^, W/ d ^, W/ d ^, W/ d ^, W/ &Z  t &Z &  t   > • Split - Sky Air • RXM-M9...
  • Page 17 ZyD D &Z &   d ^, W/ d ^, W/ d ^, W/ d ^, W/ d ^, W/ d ^, W/ &Z  t &Z &  t   > • Split - Sky Air • RXM-M9...
  • Page 18 ZyD D &Z &   &Z  t &Z &  t   > &, ZyD D   &Z &  t &Z &Z &  t   > • Split - Sky Air • RXM-M9...
  • Page 19 &syD & ZyD D   &Z & d ^, W/ d ^, W/ d ^, W/ d ^, W/ d ^, W/ d ^, W/  t &Z &Z &  t   > • Split - Sky Air • RXM-M9...
  • Page 20 & ZyD D &Z &   d ^, d ^, W/ d ^, W/ d ^, W/ d ^, W/ d ^, &Z  t &Z &  t   > • Split - Sky Air • RXM-M9...
  • Page 21 ZyD D &Z &   &Z  t &Z &  t   > &yD & ZyD D &Z &   &Z  t &Z &  t   > • Split - Sky Air • RXM-M9...
  • Page 22 ZyD D &Z &   &Z  t &Z &  t   > &, ZyD D   &Z &  t &Z &Z &  t   > • Split - Sky Air • RXM-M9...
  • Page 23 The capacities are based on the following conditions: Corresponding refrigerant piping length: ·5· m Level difference: ·0·m The air flow rate and bypass factor are mentioned in the table. 3D110095 • Split - Sky Air • RXM-M9...
  • Page 24 ZyD D &Z &   &Z  t &Z &  t   > & ' ZyD D &Z &   &Z  t &Z &  t   > • Split - Sky Air • RXM-M9...
  • Page 25  t   > && ZyD D &Z &   d ^, d ^, d ^, d ^, d ^, d ^, &Z  t &Z &  t   > • Split - Sky Air • RXM-M9...
  • Page 26 ZyD D   &Z & d ^, W/ d ^, W/ d ^, W/ d ^, W/ d ^, W/ d ^, W/  t &Z &Z &  t   > • Split - Sky Air • RXM-M9...
  • Page 27: Dimensional Drawings

    • Outdoor Unit • RXM-M9 Dimensional drawings 5 - 1 Dimensional Drawings • Split - Sky Air • RXM-M9...
  • Page 28: Centre Of Gravity

    • Outdoor Unit • RXM-M9 Centre of gravity 6 - 1 Centre of Gravity • Split - Sky Air • RXM-M9...
  • Page 29: 6 Centre Of Gravity

    • Outdoor Unit • RXM-M9 Centre of gravity 6 - 1 Centre of Gravity • Split - Sky Air • RXM-M9...
  • Page 30: Piping Diagrams

    • Outdoor Unit • RXM-M9 Piping diagrams 7 - 1 Piping Diagrams • Split - Sky Air • RXM-M9...
  • Page 31: 7 Piping Diagrams

    • Outdoor Unit • RXM-M9 Piping diagrams 7 - 1 Piping Diagrams ZyD D • Split - Sky Air • RXM-M9...
  • Page 32: Wiring Diagrams

    )HUULWH FRUH =&=&=& %OXH <6 5HYHUVLQJ VROHQRLG YDOYH FRLO +/+16(( 1RLVH ILOWHU .5B$.5B% &RQQHFWLRQ 9'9'  'LRGH 3D108900-1A NOTES: 1. Size: length 105x width 185. 2. Refer to purchasing specification AS303002 unless otherwise specified. • Split - Sky Air • RXM-M9...
  • Page 33 +/+16(( *5<  *UH\ 1RLVH ILOWHU .5B$.5B% &RQQHFWLRQ 3D108901-1  'LRGH 9'9' +LJK SUHVVXUH VZLWFK 63+63+ NOTES: 1. Size: length 105 x width 185. 2. Refer to purchasing specification AS303002 unless otherwise specified. • Split - Sky Air • RXM-M9...
  • Page 34: Sound Data

    NR55 NR50 NR50 NR45 NR45 NR40 NR40 NR35 NR35 NR30 NR30 NR25 NR25 NR20 NR20 NR15 NR15 NR10 NR10 1000 2000 4000 8000 1000 2000 4000 8000 > & > , :/^ :/^ • Split - Sky Air • RXM-M9...
  • Page 35 NR55 NR50 NR50 NR45 NR45 NR40 NR40 NR35 NR35 NR30 NR30 NR25 NR25 NR20 NR20 NR15 NR10 NR15 NR10 1000 2000 4000 8000 1000 2000 4000 8000 > & > , :/^ :/^ • Split - Sky Air • RXM-M9...
  • Page 36 NR55 NR50 NR50 NR45 NR45 NR40 NR40 NR35 NR35 NR30 NR30 NR25 NR25 NR15 NR20 NR10 NR15 NR20 NR10 1000 2000 4000 8000 1000 2000 4000 8000 > & > , :/^ :/^ • Split - Sky Air • RXM-M9...
  • Page 37: Operation Range

    • Outdoor Unit • RXM-M9 Operation range 10 - 1 Operation Range • Split - Sky Air • RXM-M9...
  • Page 39 Daikin Europe N.V. Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende Daikin Europe N.V. participates in the Eurovent Certified Performance programme for Liquid Chilling Packages and Hydronic Heat Pumps, Fan Coil Units and Variable Refrigerant Flow systems.