A. Dometic Corporation recommends the basic configuration shown on page 8 for installing this air conditioner/heat pump
system. We have found through testing that this configuration works best in most applications of this air conditioner/heat pump
system. It is the responsibility of the Installer of this system to review each RV floor plan and determine the following:
1. Duct size
2. Duct layout
3
Register size
4. Register location
5. Thermostat location
These items must be determined in conjunction with the Air Distribution System and Sizing and Design Requirements listed
in the chart on page 5.
Important:
Alternate configurations and methods may be used which still allow the air conditioner/heat pump
to operate properly; however, these alternate configurations and methods must be approved by the Dometic
Corporation in writing. The following instructions are based upon the use of Dometic 3105007.XXX Return Air Kits,
3105935.XXX Quick Cool Kits, or 3308120.XXX Genesis Air Filtration System. The 3109226.XXX and 3109407.XXX
Comfort Control Center Kits have the mounting bolts supplied for use with these kits.
B. ROOF AND CEILING OPENING PREPARATION
1. A 14-1/4" x 14-1/4" (±1/8") opening must be cut through the roof and ceiling of the RV. This opening must be located
between the roof reinforcing members.
2. Mark a 14-1/4" x 14-1/4" (±1/8") square on the roof and carefully cut the opening.
3. Using the roof opening as a guide, cut the matching hole in the ceiling.
4. The opening created must be framed to provide adequate support and prevent air from being drawn from the roof cavity.
Lumber 3/4" or more in thickness must be used. Remember to provide an entrance hole for power supply wiring and
thermostat cable.
5. The 14-1/4" x 14-1/4" (±1/8") opening is part of the return air system of the air conditioner/heat pump and must be finished
in accordance with NFPA Standard 501C Section 2.7.
6. Route a copper 12 AWG (max. length 24'), with ground, supply line from the fuse or circuit breaker box to the roof opening.
a. This supply line must be located in the front portion of the 14-1/4" x 14-1/4" (±1/8") opening.
b. The power supply MUST be on a separate 20 amp for models 579, 590, 591,59516, 600 and 630 series, and 15 amp
for models 59528, 59529 and 59530 Series Time Delay Fuse or HACR Circuit Breaker.
c. Make sure at least 15" of supply wire extends into the roof opening. This ensures easy connection at the junction
box.
d. Wiring must comply with all National, State and Local Wiring Codes.
e. Use a steel sleeve and a grommet or equivalent methods to protect the wire where it passes into the opening.
7. See Section 6. Comfort Control Center, Remote Sensor and Cable Installation.
INSTALLATION INSTRUCTIONS DUCTED CCC

5. AIR DISTRIBUTION SYSTEM INSTALLATION

There may be electrical wiring between the
roof and the ceiling. Disconnect 115 volt AC
power cord and the positive (+) 12 volt DC
terminal at the supply battery. Failure to fol-
low this instruction may create a shock haz-
ard causing death or severe personal injury.
!
WARNING