Specifications; Details For Ordering - Siemens SXL-EX Datasheet

Fire control panel

Advertisement

System Overview – (continued)
Outputs:
Bypass Outputs / Relays
System Programming:
Zone to Output Matrix and Password Maintenance
System-test features include: one-person test feature,
a lamp test, search and clear of the alarm, trouble and
supervisory history buffer.

Specifications

The fire-alarm control panel (FACP) shall be a Siemens
Fire Safety SXL-EX; shall utilize conventional zones and
shall be microprocessor based and fully field
programmable. The base panel shall include four (4)
initiating zones, relays for general alarm and trouble and
two (2) power-limited notification circuits capable of a
total of 3 Amps of power.
The system shall be expandable via an expander
module (model SZE-4X), which contains an additional
four (4) conventional zones; four (4) general-purpose
relays and four (4) general-purpose, open-collector
outputs.
The fire-alarm system shall have the following
features: subsequent alarm and trouble prompts; one
person test feature; brown out protection, and 24 or
60 hour battery backup. Model SXL-EX also has the
following selectable features: supervisory zones;
alarm verification by zone; non-latching zones; alarm,
trouble and supervisory history, NAC coding, alarm /
trouble 24-hour reminder, and zone / output bypass.
Any initiating-device circuit shall have the capability of
being mapped to any optional output, via the system-
programming function.
The FACP shall be UL / ULC Listed, and meet the
requirements of NFPA 72 for local fire alarm control
for automatic or manual service, and for sprinkler
supervisory and waterflow service.
Model SLX-EX shall meet NFPA 72 requirements for
central-station service when connected to Model 5128
or Model 5129 digital fire communicator.
The system can alternately be expanded through
the expander module (Model SZE-8AX), which has
an additional four (4) Class A (Style D) initiating
circuits. Model SZE-8AX also converts the four (4)
initiating circuits and the two (2) notification
circuits on the main SXL-EX to Style D (Class A) and
Style Z (Class A), respectively.
Industry, Inc.
s
Building Technologies Division

Details for Ordering

Model
Part
Number
Number
SXL-EX Planning Bill
500-695884
(Black Enclosure)
500-696000
SXL-EX-RED Planning Bill
500-696011
(Red Enclosure)
600-696000
SXL-EX-DF Planning Bill
500-695885
(Dead Front,
500-696000
Black Enclosure)
500-695889
SXL-EX-INT
500-695885
(International,
500-696010
Black Enclosure)
SXL Optional Modules
Model
Part
Number
Number
SZE-4X
500-696006 SXL 4-Zone Expander (with outputs)
SZE-8AX
500-696007 SXL 8-Class "A" Zone Module
SRC-8
500-692972 SXL 8-Relay Module
RPR-1
500-694998 Remote Polarized 24VDC Relay
(with SXL, MXL and System 3 FACPs)
SLT-1
500-093285 SXL Leased Line / Municipal Tie Module
MM-SX
500-696008 Meter Module for SXL-EX
LED-3
500-693062 LED-3 Annunciator
SXL Control Equipment Components
SXL-XCON
500-696000
SXL-EX Board, Transformer & Hardware
SXL
XCON
INT
SXL-EX-INT Board, Transformer
-
-
500-696010
EN-SX
500-695884
SXL-EX Enclosure, Black
EN-SXR
500-696011
SXL-EX Enclosure,
DF-SX
500-695889
SXL-EX Dead Front Kit. Black Only
FT-SX
500-695890
SXL-EX Semi-Flush Trim Kit
FT-SXR
500-696104
SXL-EX Semi-Flush Trim,
SXL-AK
500-696358
SXL-EX / ENS-S Adapter Kit
SXL-MAIN
500-695992
SXL-X Main PCB Assembly Pkg.
SXL Batteries & Power Supplies
BT-33
175-387141
6AH Battery Set
BT-34
175-387140
10AH Battery Set
BP-61
175-387194
15AH Battery Set
PAD-3
599-699189
P/S NAC EXT (6 Amps)
PAD-3R
599-699190
P/S NAC EXT,
PAD-3-MB
500-699080
Main Board Only for PAD-3
EN-PAD
310-099073
Black Enclosure for PAD-3
EN-PADR
310-099150
Red
PAD-3-UK
500-648449
PAD-3-UK Upgrade Kit
SXL Upgrade Kits
SXL-EX-UK
500-363009
SXL-EX-UK F/W Upgrade Kit
SLT-1-UK
500-699052
SLT-1F/W Upgrade Kit
LED-UK
500-696205
LED-3/4 Upgrade Kit
Digital Fire Communicators
5128C
500-693213
4-Channel Slave Communicator
5129
500-693214
4-Channel Communicator [in enclosure]
5230K
500-693215
Programmer / Annunciator [
TIK-5128
500-693218
(1) Dual-Pack-RJ331X Block & Cord
Note:
Model BP-61 requires a separate enclosure (i.e. − BB-55)
Description
EN-SX Enclosure
SXL-XLCON
EN-SX Enclosure (Red)
SXL-XLCON
EN-SX Enclosure
SXL-XLCON
DF-SX Dead Front
EN-SX Enclosure
SXL-EX-INT Board,
Transformer & Hardware
Description
Hardware
&
Red
Red
Red
Enclosure for PAD-3
5128 / 5129
]