FIGURE 2
RECOMMENDED ELEVATED INSTALLATION

3.7 Factory-Preferred Tie-Down Method

IMPORTANT: The Manufacturer approved/recommended method is a guide to secur-
ing equipment for wind and seismic loads. Other methods might provide the same
result, but the Manufacturer method is the only one endorsed by Manufacturer for
securing equipment where wind or earthquake damage can occur. Additional informa-
tion is available in the PTS (Product Technial Support) section of the Manufacturer
website Rheemote.net and an be found as a listing under each outdoor model. If you
do not have access to this site, your Distributor can offer assistance.

4.0 REFRIGERANT CONNECTIONS

All units are factory charged with Refrigerant 410A. All models are supplied with
service valves. Keep tube ends sealed until connection is to be made to prevent
system contamination.
4.1 Tools Required For Installing & Servicing R-410A Models
Manifold Sets:
-Up to 800 PSIG High side
-Up to 250 PSIG Low Side
-550 PSIG Low Side Retard
Manifold Hoses:
-Service Pressure Rating of 800 PSIG
Recovery Cylinders:
-400 PSIG Pressure Rating
-Dept. of Transportation 4BA400 or BW400