Rheem RJNL-A036CK Installation Instructions Manual

Rheem RJNL-A036CK Installation Instructions Manual

Rjnl series; rjpl series package heat pumps

Advertisement

INSTALLATION INSTRUCTIONS
PACKAGE HEAT PUMPS
RJNL 13 SEER SERIES (3-5 TON)
RJNL 11.0 EER SERIES (6 TON)
RJPL 14 SEER SERIES (3-5 TON)
FEATURING INDUSTRY STANDARD R-410A REFRIGERANT
!
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION!
!
WARNING
THESE INSTRUCTIONS ARE INTENDED AS AID TO
QUALIFIED, LICENSED SERVICE PERSONNEL FOR
PROPER INSTALLATION, ADJUSTMENT AND
OPERATION OF THIS UNIT. READ THESE
INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING
INSTALLATION OR OPERATION. FAILURE TO FOLLOW
THESE INSTRUCTIONS MAY RESULT IN IMPROPER
INSTALLATION, ADJUSTMENT, SERVICE OR
MAINTENANCE POSSIBLY RESULTING IN FIRE,
ELECTRICAL SHOCK, PROPER DAMAGE, PERSONAL
INJURY OR DEATH.
PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN
DO NOT DESTROY THIS MANUAL
ISO 9001:2008
(14 SEER
MODELS ONLY)
SUPERSEDES 92-23577-77-03
92-23577-77-04

Advertisement

Table of Contents
loading

Summary of Contents for Rheem RJNL-A036CK

  • Page 1 INSTALLATION INSTRUCTIONS PACKAGE HEAT PUMPS RJNL 13 SEER SERIES (3-5 TON) RJNL 11.0 EER SERIES (6 TON) RJPL 14 SEER SERIES (3-5 TON) FEATURING INDUSTRY STANDARD R-410A REFRIGERANT RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION! WARNING THESE INSTRUCTIONS ARE INTENDED AS AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT.
  • Page 2: Table Of Contents

    I.TABLE OF CONTENTS I. Table of Contents ..........2 II.
  • Page 3: Safety Information

    II. SAFETY INFORMATION WARNING THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUST- MENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELEC- TRICAL SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
  • Page 4 WARNING DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT RETURN DUCTWORK TO ANY OTHER HEAT PRODUCING DEVICE SUCH AS A FIREPLACE INSERT, STOVE, ETC. UNAUTHORIZED USE OF SUCH DEVICES MAY RESULT IN FIRE, CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE, SEVERE PERSONAL INJURY OR DEATH. WARNING THE UNIT MUST BE PERMANENTLY GROUNDED.
  • Page 5: Introduction

    Recognize this symbol as an indica- tion of Important Safety Information! III. INTRODUCTION This booklet contains the installation and operating instructions for your package heat pump. There are a few precautions that should be taken to derive maximum satisfaction from it. Improper installation can result in unsatisfactory operation or dangerous condi- tions.
  • Page 6: Checking Product Received

    Recovery Cylinders: -400 PSIG Pressure Rating -Dept. of Transportation 4BA400 or BW400 CAUTION R-410A systems operate at higher pressures than R-22 systems. Do not use R-22 service equipment or components on R-410A equipment. IV. CHECKING PRODUCT RECEIVED Upon receiving the unit, inspect it for any damage from shipment. Claims for damage, either shipping or concealed, should be filed immediately with the shipping company.
  • Page 7 FIGURE 1 UNIT DIMENSIONS RJNL/RJPL 3-5 TON ILL I316 FIGURE 2 UNIT DIMENSIONS RJNL/RJPL 3-5 TON ILL I305...
  • Page 8 FIGURE 3 UNIT DIMENSIONS RJNL/RJPL 3-5 TON ⁄ ⁄ ⁄ ⁄ ⁄ ILL I304 FIGURE 4 UNIT DIMENSIONS RJNL/RJPL 3 TO 5 TON RETURN AIR FILTER (REMOVABLE PLATE) ILL I288...
  • Page 9 FIGURE 5 UNIT DIMENSIONS BASE ELECTRICAL BOTTOM VIEW ENTRY RJNL 6 TON CONDENSER COIL ⁄ ILL 1316 FIGURE 6 UNIT DIMENSIONS RJNL 6 TON ⁄ CONDENSER FAN DISCHARGE GRILLE ⁄ ⁄ CONDENSER COIL ILL1305...
  • Page 10 FIGURE 7 UNIT DIMENSIONS RJNL 6 TON ⁄ ⁄ ⁄ ILL 1304 FIGURE 8 UNIT DIMENSIONS RJNL 6 TON 25 1/8 82 1/4 ILL 1288...
  • Page 11 FIGURE 10 FIGURE 9 PACKAGED HEAT PUMP PACKAGED HEAT PUMP OUTSIDE SLAB INSTALLATION, BASEMENT OR OUTSIDE SLAB INSTALLATION, CLOSET DISTRIBUTION CRAWL SPACE DISTRIBUTION SYSTEM SYSTEM. SLAB FLOOR CONSTRUCTION 12” ” *Allow 57" for economizer on duct side. ILL I309 ILL I308 FIGURE 11 PACKAGED HEAT PUMP RIGGING FOR LIFTING...
  • Page 12: Outside Slab Installation

    FIGURE 12 PACKAGED HEAT PUMP ROOFCURB INSTALLATION ILL I301 ILL I300 e. Drain facilities and connections. f. Location for minimum noise. 2. LOCATION These units are designed for outdoor installations. They can be mounted on a slab or rooftop. They are not to be installed within any part of a structure such as an attic, crawl space, closet, or any other place where condenser air flow is restricted or other than outdoor ambient conditions prevail.
  • Page 13: Clearances

    FIGURE 13 PACKAGED HEAT PUMP FLAT ROOFTOP INSTALLATION, ATTIC OR DROP CEILING DISTRIBUTION SYSTEM. MOUNTED ON ROOFCURB. CURB MUST BE LEVEL FIGURE 14 COVER GASKET DETAIL ILL I631 ILL I310 C. CLEARANCES The following minimum clearances must be observed for proper unit performance and serviceability.
  • Page 14: Viii.filters

    FIGURE 15 CONDENSATE DRAIN WARNING DO NOT, UNDER ANY CIRCUMSTANCES, CONNECT RETURN DUCTWORK TO ANY OTHER HEAT PRODUCING DEVICE SUCH AS A FIREPLACE INSERT, STOVE, ETC. UNAUTHORIZED USE OF SUCH DEVICES MAY RESULT IN FIRE, CARBON MONOXIDE POISONING, EXPLOSION, PROPERTY DAMAGE, SEVERE PERSONAL INJURY OR DEATH.
  • Page 15: Condensate Drain

    FIGURE 16 BRANCH CIRCUIT DISCONNECT LOCATION TABLE A TO POWER WIRE SIZES AWG Copper AWG Aluminum Connector Type and Size Wire Size Wire Size (or equivalent) T&B Wire Nut T&B Wire Nut Ilsco Split Bolt AK-6 BRANCH CIRCUIT Ilsco Split Bolt AK-4 DISCONNECT Ilsco Split Bolt...
  • Page 16: Special Instructions For Power Wiring With Aluminum Conductors

    FIGURE 17 HEATER KIT INSTALLATION ILL I312 FIGURE 18 WITH ONE OUTDOOR THERMOSTAT VOLTAGE CONNECTIONS DIAGRAMS W/EMERGENCY HEAT RELAY STANDARD UNIT CONTROL THERMOSTAT WIRE PIGTAILS UNIT CONTROL SUB-BASE THERMOSTAT WIRE PIGTAILS SUB-BASE OUTDOOR THERMOSTAT GRAY W/EMERGENCY HEAT RELAY BLACK BLUE BROWN BROWN BROWN...
  • Page 17: Control Wiring

    TABLE C COPPER WIRE SIZE – AWG (1% VOLTAGE DROP) Supply Wire Length Feet Circuit Ampacity NOTE: 1. Wire size based on 60ºC type copper conductors below 100 ampacity. 2. Wire size based on 75ºC type copper conductors for 100 ampacity and above. c.
  • Page 18: Crankcase Heat

    XIV. CRANKCASE HEAT (OPTIONAL) Crankcase heat is not required on scroll type compressors, but may be necessary for difficult starting situations. XV. PRE-START CHECK 1. Is unit properly located and slightly slanted toward indoor condensate drain? 2. Is ductwork insulated, weatherproofed, with proper spacing to combustible materi- als? 3.
  • Page 19: Auxiliary Heat

    IMPORT NT: The compressor has an internal overload protector. Under some condi- tions, it can take up to 2 hours for this overload to reset. Make sure overload has had time to reset before condemning the compressor. Some units are equipped with a time delay control (TDC1). The control allows the blower to operate for up to 90 seconds after the thermostat is satisfied.
  • Page 20 DEFROST TERMINATION Once a defrost is initiated, the defrost will continue until fourteen minutes has elapsed or the coil temperature has reached the terminate temperature. The termi- nate temperature is factory set at 70°F, although the temperature can be changed to 50°F, 60°F, 70°F or 80°F by relocating a jumper on the board.
  • Page 21 To exit the lock-out mode, remove 24 volts to the defrost control by removing power to indoor air-handler/furnace or by shorting the two Exiting Lock-Out Mode: defrost control test pins together. ENHANCED FEATURE DEFROST CONTROL DIAGNOSTIC CODES No Power LED 1 LED 2 Control Board Status Coil Sensor Failure...
  • Page 22: Xx. General Data

    XX. GENERAL DATA - RJNL MODELS NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNL- Series A036CK A036CL A036CM A036DK Cooling Performance Continued -> Gross Cooling Capacity Btu [kW] 37,800 [11.08] 37,800 [11.08] 37,800 [11.08] 37,800 [11.08] EER/SEER 11.5/13 11.5/13 11.5/13 11.5/13 Nominal CFM/ARI Rated CFM [L/s] 1200/1200 [566/566]...
  • Page 23 GENERAL DATA - RJNL MODELS NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNL- Series A036DL A036DM A036JK A042CK Cooling Performance Continued -> Gross Cooling Capacity Btu [kW] 37,800 [11.08] 37,800 [11.08] 37,800 [11.08] 44,000 [12.89] EER/SEER 11.5/13 11.5/13 11.5/13 11.2/13 Nominal CFM/ARI Rated CFM [L/s] 1200/1200 [566/566] 1200/1200 [566/566]...
  • Page 24 GENERAL DATA - RJNL MODELS NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNL- Series A042CL A042CM A042DK A042DL Cooling Performance Continued -> Gross Cooling Capacity Btu [kW] 44,000 [12.89] 44,000 [12.89] 44,000 [12.89] 44,000 [12.89] EER/SEER 11.2/13 11.2/13 11.2/13 11.2/13 Nominal CFM/ARI Rated CFM [L/s] 1400/1400 [661/661] 1400/1400 [661/661]...
  • Page 25 GENERAL DATA - RJNL MODELS NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNL- Series A042DM A042JK A048CK A048CL Cooling Performance Continued -> Gross Cooling Capacity Btu [kW] 44,000 [12.89] 44,000 [12.89] 50,000 [14.65] 50,000 [14.65] EER/SEER 11.2/13 11.2/13 11.2/13 11.2/13 Nominal CFM/ARI Rated CFM [L/s] 1400/1400 [661/661] 1400/1400 [661/661]...
  • Page 26 GENERAL DATA - RJNL MODELS NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNL- Series A048CM A048DK A048DL A048DM Cooling Performance Continued -> Gross Cooling Capacity Btu [kW] 50,000 [14.65] 50,000 [14.65] 50,000 [14.65] 50,000 [14.65] EER/SEER 11.2/13 11.2/13 11.2/13 11.2/13 Nominal CFM/ARI Rated CFM [L/s] 1600/1600 [755/755] 1600/1600 [755/755]...
  • Page 27 GENERAL DATA - RJNL MODELS NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNL- Series A048JK A060CK A060CL A060CM Cooling Performance Continued -> Gross Cooling Capacity Btu [kW] 50,000 [14.65] 61,000 [17.87] 61,500 [18.02] 61,500 [18.02] EER/SEER 11.2/13 11.5/13 11.5/13 11.5/13 Nominal CFM/ARI Rated CFM [L/s] 1600/1600 [755/755] 2000/2000 [944/944]...
  • Page 28 GENERAL DATA - RJNL MODELS NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNL - Series A060DK A060DL A060DM A060JK Continued -> Gross Cooling Capacity Btu [kW] 61,000 [17.87] 61,500 [18.02] 61,500 [18.02] 61,000 [17.87] Cooling performance EER, SEER 11.5/13 11.5/13 11.5/13 11.5/13 Nominal CFM/AHRI Rated CFM [L/s]...
  • Page 29 GENERAL DATA - RJNL MODELS NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNL - Series A072CL A072CM A072DL A072DM Continued -> Gross Cooling Capacity Btu [kW] 73,000 [21.39] 73,000 [21.39] 73,000 [21.39] 73,000 [21.39] Cooling performance EER, SEER 11/NA 11/NA 11/NA 11/NA Nominal CFM/AHRI Rated CFM [L/s]...
  • Page 30 GENERAL DATA - RJNL MODELS NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJNL - Series A072YL Gross Cooling Capacity Btu [kW] 73,000 [21.39] Cooling performance EER, SEER 11/NA Nominal CFM/AHRI Rated CFM [L/s] 2400/2125 [1133/1003] AHRI Net Cooling Capacity Btu [kW] 70,000 [20.51] Net Sensible Capacity Btu [kW] 50,700 [14.85]...
  • Page 31 GENERAL DATA - RJPL MODELS NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJPL - Series A036CK A036CL A036CM A036DK Continued -> Gross Cooling Capacity Btu [kW] 37,800 [11.08] 37,800 [11.08] 37,800 [11.08] 37,800 [11.08] Cooling performance EER, SEER 12/14 12/14 12/14 12/14 Nominal CFM/AHRI Rated CFM [L/s]...
  • Page 32 GENERAL DATA - RJPL MODELS NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJPL - Series A036DL A036DM A036JK A042CK Continued -> Gross Cooling Capacity Btu [kW] 38,500 [11.28] 38,500 [11.28] 37,800 [11.08] 43,500 [12.75] Cooling performance EER, SEER 12/14 12/14 12/14 11.6/14 Nominal CFM/AHRI Rated CFM [L/s]...
  • Page 33 GENERAL DATA - RJPL MODELS NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJPL - Series A042CL A042CM A042DK A042DL Continued -> Gross Cooling Capacity Btu [kW] 44,000 [12.89] 44,000 [12.89] 43,500 [12.75] 44,000 [12.89] Cooling performance EER, SEER 11.6/14 11.6/14 11.6/14 11.6/14 Nominal CFM/AHRI Rated CFM [L/s]...
  • Page 34 GENERAL DATA - RJPL MODELS NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJPL - Series A042DM A042JK A048CK A048CL Continued -> Gross Cooling Capacity Btu [kW] 44,000 [12.89] 43,500 [12.75] 49,000 [14.36] 50,000 [14.65] Cooling performance EER, SEER 11.6/14 11.6/14 11.6/14 11.6/14 Nominal CFM/AHRI Rated CFM [L/s]...
  • Page 35 GENERAL DATA - RJPL MODELS NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJPL - Series A048CM A048DK A048DL A048DM Continued -> Gross Cooling Capacity Btu [kW] 50,000 [14.65] 49,000 [14.36] 50,000 [14.65] 50,000 [14.65] Cooling performance EER, SEER 11.6/14 11.6/14 11.6/14 11.6/14 Nominal CFM/AHRI Rated CFM [L/s]...
  • Page 36 GENERAL DATA - RJPL MODELS NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJPL - Series A048JK A060CK A060CL A060CM Continued -> Gross Cooling Capacity Btu [kW] 49,000 [14.36] 61,000 [17.87] 61,000 [17.87] 61,000 [17.87] Cooling performance EER, SEER 11.6/14 11.7/14 11.7/14 11.7/14 Nominal CFM/AHRI Rated CFM [L/s]...
  • Page 37 GENERAL DATA - RJPL MODELS NOMINAL SIZES 3-5 TONS [10.6-17.6 kW] Model RJPL - Series A060DK A060DL A060DM A060JK Gross Cooling Capacity Btu [kW] 61,000 [17.87] 61,000 [17.87] 61,000 [17.87] 61,000 [17.87] Cooling performance EER, SEER 11.7/14 11.7/14 11.7/14 11.7/14 Nominal CFM/AHRI Rated CFM [L/s] 2000/1850 [944/873] 2000/1850 [944/873]...
  • Page 38: Miscellaneous

    XXI. MISCELLANEOUS ELECTRICAL DATA – RJNL- SERIES A036CK A036CL A036CM A036DK A036DL A036DM Unit Operating Voltage Range 187-253 187-253 187-253 414-506 414-506 414-506 Volts 208/230 208/230 208/230 Minimum Circuit Ampacity 19/19 18/18 19/19 Minimum Overcurrent Protection Device Size 25/25 20/20 25/25 Maximum Overcurrent Protection Device Size...
  • Page 39 ELECTRICAL DATA – RJNL- SERIES A036JK A042CK A042CL A042CM A042DK A042DL Unit Operating Voltage Range 187-253 187-253 187-253 187-253 414-506 414-506 Volts 208/230 208/230 208/230 208/230 Minimum Circuit Ampacity 27/27 23/23 22/22 22/22 Minimum Overcurrent Protection Device Size 35/35 30/30 25/25 30/30 Maximum Overcurrent...
  • Page 40 ELECTRICAL DATA – RJNL- SERIES A042DM A042JK A048CK A048CL A048CM A048DK Unit Operating Voltage Range 414-506 187-253 187-253 187-253 187-253 414-506 Volts 208/230 208/230 208/230 208/230 Minimum Circuit Ampacity 28/28 23/23 22/22 23/23 Minimum Overcurrent Protection Device Size 35/35 30/30 25/25 30/30 Maximum Overcurrent...
  • Page 41 ELECTRICAL DATA – RJNL- SERIES A048DL A048DM A048JK A060CK A060CL A060CM Unit Operating Voltage Range 414-506 414-506 187-253 187-253 187-253 187-253 Volts 208/230 208/230 208/230 208/230 Minimum Circuit Ampacity 33/33 25/25 26/26 26/26 Minimum Overcurrent Protection Device Size 40/40 30/30 30/30 30/30 Maximum Overcurrent...
  • Page 42 ELECTRICAL DATA – RJNL- SERIES A060DK A060DL A060DM A060JK A072CL A072CM A072DL Unit Operating Voltage Range 414-506 414-506 414-506 187-253 187-253 187-253 414-506 Volts 208/230 208/230 208/230 Minimum Circuit Ampacity 39/39 34/34 34/34 Minimum Overcurrent Protection Device Size 45/45 40/40 40/40 Maximum Overcurrent Protection Device Size...
  • Page 43 ELECTRICAL DATA – RJNL- SERIES A072DM A072YL Unit Operating Voltage Range 414-506 518-633 Volts Minimum Circuit Ampacity Minimum Overcurrent Protection Device Size Maximum Overcurrent Protection Device Size Volts Phase 3450 3450 HP, Compressor 1 7 1/2 7 1/2 Amps (RLA), Comp. 1 10.9 Amps (LRA), Comp.
  • Page 44 ELECTRICAL DATA – RJPL- SERIES -A036CK -A036CL -A036CM -A036DK -A036DL -A036DM -A036JK Unit Operating Voltage Range 187-253 187-253 187-253 414-506 414-506 414-506 187-253 Minimum Circuit Ampacity 17/17 18/18 18/18 24/24 Minimum Overcurrent Protection Device Size 20/20 20/20 25/25 30/30 Maximum Overcurrent Protection Device Size 25/25 25/25...
  • Page 45 ELECTRICAL DATA – RJPL- SERIES -A042CK -A042CL -A042CM -A042DK -A042DL -A042DM -A042JK Unit Operating Voltage Range 187-253 187-253 187-253 414-506 414-506 414-506 187-253 Minimum Circuit Ampacity 21/21 22/22 22/22 26/26 Minimum Overcurrent Protection Device Size 25/25 25/25 30/30 35/35 Maximum Overcurrent Protection Device Size 30/30 30/30...
  • Page 46 ELECTRICAL DATA – RJPL- SERIES -A048CK -A048CL -A048CM -A048DK -A048DL -A048DM -A048JK Unit Operating Voltage Range 187-253 187-253 187-253 414-506 414-506 414-506 187-253 Minimum Circuit Ampacity 21/21 22/22 23/23 31/31 Minimum Overcurrent Protection Device Size 25/25 25/25 30/30 40/40 Maximum Overcurrent Protection Device Size 30/30 35/35...
  • Page 47: Electrical Data

    ELECTRICAL DATA – RJPL- SERIES -A060CK -A060CL -A060CM -A060DK -A060DL -A060DM -A060JK Unit Operating Voltage Range 187-253 187-253 187-253 414-506 414-506 414-506 187-253 Minimum Circuit Ampacity 25/25 26/26 26/26 39/39 Minimum Overcurrent Protection Device Size 30/30 30/30 30/30 45/45 Maximum Overcurrent Protection Device Size 40/40 40/40...
  • Page 48: Indoor Airflow Performance

    INDOOR AIRFLOW PERFORMANCE FOR 3-5 TON PACKAGE HEAT PUMPS – RJNL DIRECT DRIVE...
  • Page 49 INDOOR AIRFLOW PERFORMANCE FOR 3-5 TON PACKAGE HEAT PUMPS – RJPL DIRECT DRIVE...
  • Page 50 INDOOR AIRFLOW PERFORMANCE – RJNL...
  • Page 51 INDOOR AIRFLOW PERFORMANCE – RJNL...
  • Page 52: Indoor Airflow Performance

    INDOOR AIRFLOW PERFORMANCE – RJNL...
  • Page 53: Heater Kits Characteristics

    AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJNL...
  • Page 54 AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJNL...
  • Page 55 AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJNL...
  • Page 56 AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJNL...
  • Page 57 AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJNL...
  • Page 58 AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJNL...
  • Page 59 AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJNL...
  • Page 60 AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION...
  • Page 61 AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJPL...
  • Page 62 AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJPL...
  • Page 63 AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJPL...
  • Page 64 AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJPL...
  • Page 65 AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJPL...
  • Page 66: Heater Kits Characteristics

    AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION – RJPL...
  • Page 67: Wiring Diagrams

    FIGURE 19 WIRING DIAGRAM...
  • Page 68 FIGURE 20 WIRING DIAGRAM...
  • Page 69 FIGURE 21 WIRING DIAGRAM...
  • Page 70 FIGURE 22 WIRING DIAGRAM...
  • Page 71 FIGURE 23 WIRING DIAGRAM...
  • Page 72 FIGURE 24 WIRING DIAGRAM...
  • Page 73 FIGURE 25 WIRING DIAGRAM...
  • Page 74 FIGURE 26 WIRING DIAGRAM...
  • Page 75 FIGURE 27 WIRING DIAGRAM...
  • Page 76: Wiring Diagrams

    FIGURE 28 WIRING DIAGRAM...
  • Page 80 5 TON – 13 SEER...
  • Page 81 5 TON – 14 SEER...
  • Page 82 6 T O N H P ( R 4 1 0 A ) SYSTEM CHARGE CHART (COOLING) S U C T I O N P R E S S U R E - P S I G SYSTEM CHARGE CHART (HEATING) S U C T I O N P R E S S U R E - P S I G 92-102380-06-00...
  • Page 83: Troubleshooting

    TROUBLE SHOOTING CHART WARNING DISCONNECT ALL POWER TO UNIT BEFORE SERVICING. CONTACTOR MAY BREAK ONLY ONE SIDE. FAILURE TO SHUT OFF POWER CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH. SYMPTOM POSSIBLE CAUSE REMEDY Unit will not run •...
  • Page 84 CM 0710...