Cooling Mechanical Checks Flow Chart - Rheem R-410A Installation Instructions Manual

Prl-jec series two-stage heat pump outdoor units
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

18.4 Cooling Mechanical Checks Flow Chart

High Head Pressure
Inoperative Outdoor Fan
Higher than Ambient
Air Entering Outdoor Coil
Wrong Outdoor Fan Rotation
42
Dirty Outdoor Coil
Overcharge
Recirculation of
Outdoor Air
Non-condensibles
Unit Running?
YES
Pressure problems?
Low Head Pressure
Low on Charge
Open IPR Valve
Low Ambient Temperature
Inoperative Compressor
Valves
Outdoor Check Valve
Closed
Restricted Indoor
Metering Device
Restricted
Filter Drier
NO
Go to Electrical
Checks Flow Chart
Low Suction Pressure
Dirty Filters
Dirty Indoor Coil
Inadequate Indoor Air Flow
Inoperative Indoor Blower
Low on Charge
Restricted Indoor
Metering Device
Restriction in System
Recirculation of
Indoor Air
Wrong Indoor
Blower Rotation
Inadequate Ducts
Outdoor Check Valve Closed
Restricted Filter Drier

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Prl-jec series024jec036jec048jec060jec

Table of Contents