Section 6. Maintenance; Care And Maintenance; Pressure Relief Valve - Pentair Pool Products 175K BTU/HR Operation & Installation Manual

Pool & spa heater 120/240 vac natural gas/lp gas
Table of Contents

Advertisement

Section 6. Maintenance

Maintenance Instructions

CARE AND MAINTENANCE

Risk of fire or explosion from flammable vapors. Do not store gasoline, cleaning fluids, varnishes, paints, or other volatile
flammable liquids near heater or in the same room with heater.
The following maintenance is recommended every six months and at the start of every swimming season:
1. Inspect the heater panels and venting system to make sure that there are no obstructions to the flow of ventilating air
or burner exhaust. Check that room air intakes are open and clear of obstructions.
2. Keep the area in and around the heater clear and free from combustible materials, gasoline and other flammable
vapors and corrosive liquids.
3. Test the operation of the pressure relief valve by lifting the valve lever.
4. Test for proper operation of the pressure switch. (See "WATER PRESSURE SWITCH" for testing instructions).
5. On enclosed installations with high-temperature Special Gas Vent systems, repeat the "Final Installation Check,"
page
27. Check for evidence of joint leakage. Make sure that joints have not slipped partially or completely apart.
Check pipe and fittings for cracks or breaks. The combustion air blower is permanently lubricated, and does not
require periodic lubrication. The burner does not require maintenance or adjustment by the user. Call a qualified
service technician if you suspect that the burner may require maintenance.

PRESSURE RELIEF VALVE

Canadian code requires and some U.S. local codes may require installation of a
pressure relief valve (PRV). Purchase separately and install a 3/4" pressure
relief valve complying with the ANSI/ASME Boiler and Pressure Vessel Code,
having a capacity equal to the Btu/hr rating of the heater. The relief pressure of
the valve MUST NOT EXCEED 50 PSI.
The relief valve must be installed vertically. To install the valve, use a 3/4" x 2"
brass nipple at the manifold, the two brass elbows and nipples are (user supplied),
as illustrated in
Figure
34. No valve is allowed to be placed between the manifold
adapter and the relief valve.
To avoid water damage or scalding from operation of the relief valve, install a
drain pipe in the outlet of the pressure relief valve that will direct water discharging
from the valve to a safe place for disposal. Do not install any reducing couplings
or valves in the drain pipe. The drain pipe must be installed so as to allow complete
drainage from the valve and drain line. The relief valve should be tested at
least once a year by lifting the valve lever.
Explosion hazard. Any heater installed with restrictive devices in the piping system downstream from the heater, (including
check valves, isolation valves, flow nozzles, or therapeutic pool valving), must have a relief valve installed as described above.
Rev. C 10-5-07
WARNING
WARNING
4 5
Drill thru the NPT Port, then
use a 3/4" Brass Nipple and
Elbow (user supplied) for a
PRV Installation.
Figure 34.
P/N 472592

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

400k btu/hr asme200k btu/hr250k btu/hr hd300k btu/hr

Table of Contents