RBI Dominator Series Installation & Operating Instructions Manual page 32

Finned copper tube gas boilers & water heater
Table of Contents

Advertisement

Relay Board
Th e relay board is located in the control tray. It provides sequencing
of the gas valves and blower(s) based on the staging controller's
input. It also provides the following time delays for proper unit
operation:
• A 40 second prepurge when stage 1 is energized.
• A 10 second pressure switch sequencing delay when the blowers
switch from low fi re to high fi re. Th e delay enables the blower to
come up to speed before the high pressure side of the pressure
switch confi rms proper air fl ow.
Th ese time delays are set within the separate time delay board
connected to the relay board.
Gas Pressure Switch
An optional low and/or high gas pressure switch will shut
down the 24V circuit if excessively high or low gas pressure exists
in the gas train or supply piping.
BTC Staging Control
Th e staging control is located at the front of the control tray. It
utilizes various temperature sensors to calculate boiler/water heater
demand and adjust the stages as required. Various features of the
control can be adjusted from the 3-butt on panel on the controller.
To change sett ings of the staging controller, press and hold all three
butt ons approximately 2 seconds until the "adjust" screen appears,
then release them. Th e staging controller provides 6 modes of
operation based on the requirements of the system. Th e desired
mode can be set manually from the controller. Each mode is defi ned
below. Refer to the control manufacturer' s documentation for more
information on the controller and its adjustment features.
At the rear of the controller, two DIP switches are provided to allow
an installer to modify staging control operation. Th ese switches are
factory set to provide a "lockout" with minimum adjustment
capabilities in the fi eld. However, for experienced installers and
operators, changing these switch sett ings can off er many fi ne-tuning
features. Consult the control manufacturer's documentation for
more information on the controller and its adjustment features.
DO NOT change DIP switch or controller sett ings
unless you have completely read and understood this
document and the control manufacturer' s instructions.
Doing otherwise will lead to improper stage control
operation.
Mode 1: Setpoint control. Dominator piped in parallel with
the system. Th e fi ring stages are operated to provide a setpoint
temperature at the boiler/water heater outlet.
SETPOINT OPERA TION - Th e control operates the boiler stages
to maintain the programmed temperature at the boiler/water heater
outlet sensor whenever a heat demand is present.
32
F F
Finned copper tube gas boilers & water heaters – Boiler Manual
Fi
d
b
b il
&
h
B il
M
Mode 2: Setpoint control. Dominator piped in primary/
secondary confi guration. An additional system sensor is required
to properly control the system supply (primary loop) temperature.
Th e fi ring stages are operated to provide a setpoint temperature in
the primary loop.
SETPOINT OPERA TION - Th e control operates the boiler/water
heater stages to maintain the programmed temperature at the supply
sensor (primary loop sensor) whenever a heat demand is present.
Mode 3: Domestic Hot Water (DHW) generation. Dominator
piped in parallel with the storage tank. DHW demand from sensor
located in tank or pool supply pipe. Th e fi ring stages are operated
to provide a setpoint temperature and maintain DHW tank
temperature.
DHW OPERA TION - Th e control operates to maintain the
programmed tank target temperature at the outlet sensor whenever
a DHW demand is present. A DHW demand is generated whenever
the temperature sensed by the DHW sensor drops below the
programmed tank target temperature by 1/2 the programmed
diff erential, adjustable from 2 to 10°F, -17 to -12°C. Th e demand
remains until the temperature sensed by the DHW sensor rises
above the programmed tank target temperature plus 1/2 the
programmed diff erential.
Mode 4: Outdoor reset control. Dominator piped in parallel
with the system. Th e fi ring stages are operated to provide outdoor
reset temperature control at the boiler/water heater outlet.
OUTDOOR RESET OPERA TION - Th e control operates the
water heater/boiler stages to maintain the calculated target supply
temperature at the boiler outlet sensor. Th e temperature is calculated
by the outdoor reset feature, which increases the target boiler outlet
temperature as outdoor temperature drops. Whenever the outdoor
temperature is greater than the WWSD (Warm Weather Shut Down)
sett ing, the control ignores the call for heat.
OUTDOOR RESET WITH DHW OPERA TION - A DHW tank
controlled by a pump provides reset override whenever DHW
generation is required. In Mode 4, reset override will occur if
the staging controller receives a signal across the "STPT DEM"
and "DEM SIG" terminals of the terminal strip. (i.e., closing a tank
aquastat switch wired to these terminals). In this case, the control
will temporarily override outdoor reset and increase the target
temperature to 180°F, 82°C to provide suffi cient heat to satisfy
the DHW requirement.
Mode 5: Outdoor reset control. Dominator piped in primary/
secondary confi guration. An additional system sensor is required
to properly control the system supply (primary loop) temperature.
Th e fi ring stages are operated to provide outdoor reset temperature
control in the primary loop.
OUTDOOR RESET OPERA TION - Th e control operates the
water heater/boiler stages to maintain the calculated target supply
temperature at the supply sensor. Th e temperature is calculated by
the outdoor reset feature, which increases the target supply tem-
perature as outdoor temperature drops. Whenever the outdoor
temperature is greater than the WWSD (Warm Weather Shut Down)
sett ing, the control ignores the call for heat.
l

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents