Common Vent Systems - RBI Dominator Series Installation & Operating Instructions Manual

Finned copper tube gas boilers & water heater
Table of Contents

Advertisement

Outdoor Venting
Figure 8
Multiple outdoor Units
Figure 9
12
F F
Finned copper tube gas boilers & water heaters – Boiler Manual
Fi
d
b
b il
&
h
B il
M

COMMON VENT SYSTEMS

If an existing boiler/water heater is removed from a common venting
system, the common venting system may then be too large for the
proper venting of the remaining appliances connected to it. At the
time of removal of an existing boiler/water heater, the following
steps shall be followed with each appliance remaining connected
to the common venting system placed in operation, while the other
appliances remaining connected to the common venting system
are not in operation.
Au moment du retrait d'une chaudière existante, les mesures suivantes
doivent être prises pour chaque appareil toujours raccordé au système
d' é vacuation commun et qui fonctionne alors que d'autres appareils
toujours raccordés au système d' é vacuation ne fonction-nent pas:
système d' é vacuation
a) Seal any unused openings in the common venting system.
Sceller toutes les ouvertures non utilisées du système d' é vacuation.
b) Visually inspect the venting system for proper size and horizontal
pitch and determine there is no blockage or restriction, leakage,
corrosion and other defi ciencies which could cause an unsafe
condition.
Inspecter de façon visuelle le système d'évacu-ation pour
déterminer la grosser et l'inclinaison horizontale qui conviennent
et s' a ssurer que le système est exempt d' o bstruction, d' é tranglement
de fruite, de corrosion et autres défaillances qui pourraient
présenter des risques.
c) Insofar as is practical, close all building doors and windows and
all doors between the space in which the appliances remaining
connected to the common venting system are located and other
spaces of the building. Turn on clothes dryers and any appliance
not connected to the common venting system. Turn on any
exhaust fans, such as range hoods and bathroom exhaust, so
they will operate at maximum speed. Do not operate a summer
exhaust fan for a boiler installation. Close fi replace dampers.
Dans la mesure du possible, fermer toutes les portes et les fenêtres
du bâtiment et toutes les portes entre l'espace où les appareils
toujours raccordés du système d'évacuation sont installés et les
autres espaces du bâtiment. Mett re en marche les sécheuses, tous
les appareils non raccordés au système d' é vacuation commun et
tous les ventilateurs d'extraction comme les hott es de cuisinère
et les ventilateurs des salles de bain. S'assurer que ces ventilateurs
fonctionnent à la vitesse maximale. Ne pas faire fonctionner les
ventilateurs d' é té. Fermer les registres des cheminées.
d) Place in operation the appliance being inspected. Follow the
lighting instructions. Adjust thermostat so appliance will operate
continuously.
Mett re l'appareil inspecté en marche. Suivre les instructions
d' a llumage. Régler le thermostat de façon que l' a ppareil fonctionne
de façon continue.