Modifying Service Settings; Control Panel; Display; Scroll Keys - Atlas Copco GA55 User Manual

Stationary air compressors
Hide thumbs Also See for GA55:
Table of Contents

Advertisement

2. Press the key <<Slct>> (select): a screen similar to the
one shown below appears (Fig. 12.13).
Cool water out
Warn
Max
C
Menu
Mod
F1
F2
Fig. 12.13. Example of a modifying screen (protection settings)
The example in Fig. 12.13 indicates:
-
On line 1, the name of the sensor (<<cool water out>>)
-
On line 2, the type of parameter (<<warn>>) and the
programmed maximum (<<Max. 60>>)
-
On line 3, the unit and actual value (<<45>>)
3. To modify the warning level, press the key <<Mod>>
(modify) and use the scroll keys (6-Fig. 2.1).
4. Use the key <<Prog>> to program the new value or the key
<<Canc>> to cancel the modification (the original value
will be retained).
Notes
The regulator will not accept new values beyond the
limitations. See section 18. It is possible to check the
limitations by selecting <<Lim>> (limits).
5. The arrow on the screen (Fig. 12.13) indicates to use the
scroll key ↓ (6-Fig. 2.1) to show the programmed delay for
the warning signal; see Fig. 12.14.
Cool water out
Delay at signal
sec
Menu
Mod
F1
F2
Fig. 12.14. Example of a modifying screen (protection settings)
6. If necessary, use the key <<Mod>> and the scroll keys for
modifying.
7. Use the key <<Prog>> to program the new value or the key
<<Canc>> to cancel the operation (the original value will
be retained). See also step 4.
8. The arrow on the screen (Fig. 12.14) indicates to use the
scroll key ↓ (6-Fig. 2.1) to show the programmed delay
during start; see Fig. 12.15.
Cool water out
Delay at start
sec
Menu
Mod
F1
F2
Fig. 12.15. Example of a modifying screen (protection
settings)
18
9. Consult steps 6 and 7 if modifying is desired.
1. Call up the modify settings submenu and select the option
60
45
2. The first option of a list of programmable service settings
F3
Oil lifetime
Menu
F1
Fig. 12.16. Example of a modifying screen (service settings)
3. Select the parameter to be modified by pressing the key
Running hours
Serv
Hrs
Menu
F1
Fig. 12.17. Example of a modifying screen (service settings)
4. To modify the setting of the running hours, press the key
0
5. Use the key <<Prog>> to program the new value or the key
F3
-
-
Footnotes chapter 12
1) If required, the automatic restart function after voltage failure
0
F3
<<service settings>>. See section 12.2.
is shown. See section 12.1 for the list of all programmable
parameters. Use the scroll keys (6-Fig. 2.1) to select the
parameter to be modified, e.g. oil lifetime (Fig. 12.16).
Slct
F2
<<Slct>> (select). If selecting the oil lifetime, a screen
similar to the one in Fig. 12.17 appears:
Max
Mod
F2
<<Mod>> (modify) and then use the scroll keys (6-Fig. 2.1).
<<Canc>> to cancel the modification operation (the original
value will be retained).
Notes
The regulator will not accept new values beyond the
limitations. See section 18.
It is possible to check the limitations which are valid for
the parameter to be modified by selecting <<Lim>> (limits).
can be activated by Atlas Copco. The power recovery time (the
period within which the voltage must be restored to have an
automatic restart) can be set between 1 and 254 seconds or to
symbol 00!. If the power recovery time is set to 00!, the
compressor will always restart after a voltage failure, no
matter how long it takes to restore the voltage. Provide a label
near to the control panel warning the operator that the compressor
automatically restarts if the voltage is restored.