Conversion - Worcester GreenStart 25Si Instruction Manual

Wall hung rsf gas-fires condensing combination boiler for sealed central heating systems and mains fed domestic hot water
Table of Contents

Advertisement

A
4.1
A
D
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 25Si/30Si
8 716 107 337b (11/05)
1.1
2.1
B
E
Code plugs
25kW NG
25kW LPG
30kW NG
30kW LPG
L. P. G. CONVERSION
1.2
I S O LATE
SUPPLY AND REMOVE OUTER CASE
AS SHOWN IN THE INSTALLATION,
C O M M I S S I O N I N G & S E RVI C I N G
INSTRUCTIONS
THE CONVERSION MUST BE CARRIED OUT
BY A COM PETE NT PE R SON. IT M UST NOT
B E AT T E M P T E D U N L E S S T H E P E R S O N
C A R R Y I N G O U T T H E C O N V E R S I O N I S
EQUIPPED WITH A COMBUSTION ANALYSER
2.2
C O N F O R M I N G
COMPETENT IN IT'S USE.
Important: The appliance shall not be installed
into a room or internal space below ground
level when it is intended for use with LPG
(propane - G31). This does not preclude the
installation into a room or space which is a
basement on one side of the building but open
to ground on the opposite side.
Installation Regulations
In addition to those specified in the main
booklet the following standard applies when
2.3
converting to an LPG appliance: BS 5842
Domest ic
Installations.
All conversions will require the air gas ratio to
be set correctly for the gas used. The
procedure for setting the air gas ratio is on
page 52.
1. Moving boiler control to service
position
Remove boiler case, as described on page
36.
1.1 Remove screw (A) from retaining bracket.
3
1.2 Lower control panel into service position.
2. Gas valve
Isolate gas supply at boiler gas cock.
2.1 Remove wire clip from gas valve outlet then
pull gas adjustment assembly free from
plastic connector and pull forward clear of
case.
C
2.2 Undo bottom gas connection to gas valve.
2.3 Undo two securing screws (B) on the
underside of casing.
Pull valve up and forward out of boiler.
Disconnect electrical connections.
Fit plastic retaining nut to the outlet of the
4.2
gas valve from the kit and hand tighten.
Replace valve with new seals.
Check for gas soundness.
3. Gas adjuster
Twist retaining clip (C) to release then
remove clip and tube.
Refit new adjuster and secure with clip.
Coloured red for LPG or black for NG.
4. Code plug
4.1 Remove 3 screws (D) retaining plastic
cover at rear of control box and remove.
4.2 Replace code plug (E) with new one
supplied with conversion kit.
Replace plastic cover.
Place control in normal position and secure
with screw.
-
104
TH E GAS / AI R R ATI O M U ST B E
R ESET AFTE R CONVE R SION. TH E
-
105
P R O C E D U R E C AN B E F O U N D I N
-
106
THE REPLACEMENT PARTS SECTION
-
107
OF THIS MANUAL.
MAI N S
E LE CTR I C AL
TO
B S
79 2 7
A N D
I S
Propane
Gas
Burning
L.P.G. CONVERSION
54