SMMS Concealed Duct High Static Pressure Type
5

Fan Characteristics

Install volume dumpers to the air discharge ducts. Adjust the air volume within the range of 80 to 120 % of the
standard air volume.
AP018
Standard air volume: 900 m
1.5
High static pressure tap
Medium static pressure tap
1.0
Low static pressure tap
0.5
250
50 Hz
60 Hz
200
150
100
50
0
700
800
900
1000
3
Air volume (m
/h)
AP036
Standard air volume: 1600 m
2.5
High static pressure tap
2.0
Medium static pressure tap
1.5
Low static pressure tap
1.0
250
50 Hz
60 Hz
200
150
100
50
0
1400
1500
1600
1700
3
Air volume (m
/h)
15-EN
Installation Manual
AP024, AP027
3
Standard air volume: 1320 m
/h
High static pressure tap
2.0
Medium static pressure
tap
1.5
Low static pressure tap
1.0
300
250
200
150
100
50
1320
0
1000
1100
1200
1300
1400
1100
3
Air volume (m
/h)
AP048
3
/h
Standard air volume: 2100 m
3.0
High static pressure tap
2.5
2.0
Medium static pressure tap
1.5
Low static pressure tap
0.5
250
200
150
100
50
2100
0
1800
1500
2000
3
Air volume (m
/h)
SMMS Concealed Duct High Static Pressure Type
Wire connection change of fan motor
Connecting wire of the fan motor has been connected to [F2] [External static pressure 14 mmAq (137 Pa)] at
shipment of the factory.
If it is necessary to change the external static pressure in accordance with duct resistance, change the connection.
3
/h
FM
Fan motor
50 Hz
Orange (Factory default)
60 Hz
Lead wire for changing the external static pressure.
When changing the external static pressure is
necessary, change connection of this lead wire.
REQUIREMENT
If changing the external static pressure, write the static pressure after change in the nameplate of the unit.
Terminal clock No.
1500
1600
F1
F2
3
F3
/h
F4
50 Hz
60 Hz
2500
– 8 –
The brown lead wire is attached to AP048.
(Pay attention to change the wiring.)
Control
substrate
F1
F2
F3
F4
4P Control P.C. board
Fan motor wiring
External static pressure (Pa)
Model MMD-
AP018 to AP036
AP048
Blue (50/60 Hz)
Orange (50/60 Hz)
(137) 14
Black (50 Hz/60 Hz)
Black (60 Hz)
(196) 20
Brown (50 Hz)
(196) 20
Installation Manual
Electrical control box
2P Control P.C. board
Remarks
mmAq
(69) 7
Factory default
EN