Group Control - Toshiba MMD-AP0184H-E Installation Manual

Concealed duct high static pressure type air conditioners
Hide thumbs Also See for MMD-AP0184H-E:
Table of Contents

Advertisement

SMMS Concealed Duct High Static Pressure Type
2
Each time
button is pushed, indoor
unit numbers in the control group change
cyclically. Select the indoor unit to change
settings for.
The fan of the selected unit runs and the louvers
start swinging. The indoor unit for change settings
can be confirmed.
3
Specify CODE No. [
] with "TEMP."
buttons.
4
Select SET DATA [
] with "TIME"
buttons.
5
Push
button. When the display changes
from flashing to lit, the setup is completed.
• To change settings of another indoor unit,
2
repeat from Procedure
.
• To change other settings of the selected indoor
3
unit, repeat from Procedure
.
Use
button to clear the settings. To make
settings after
button was pushed, repeat from
2
Procedure
.
6
When settings have been completed, push
button to determine the settings.
When
button is pushed,
flashes and
then the display content disappears and the air
conditioner enters the normal stop mode.
(While
is flashing, no operation of the
remote controller is accepted.)
27-EN
Installation Manual
Filter sign setting
According to the installation condition, the filter sign
term (Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
1
2
3
4
5
6
(
).
3
• For the CODE No. in Procedure
, specify [01].
4
• For the [SET DATA] in Procedure
, select the SET
DATA of filter sign term from the following table.
SET DATA
Filter sign term
0000
None
0001
150 H
/
2500 H
0002
(Factory default)
0003
5000 H
/
0004
10000 H
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator or other machinery to
circulate heat air near the ceiling.
Follow to the basic operation procedure
1
2
3
4
5
6
(
).
3
• For the CODE No. in Procedure
, specify [06].
4
• For the set data in Procedure
, select the SET
DATA of shift value of detection temperature to be
set up from the following table.
SET DATA
Detection temperature shift value
0000
No shift
0001
+1 °C
+2 °C
0002
(Factory default)
0003
+3 °C
0004
+4 °C
0005
+5 °C
0006
+6 °C
SMMS Concealed Duct High Static Pressure Type
Remote controller sensor
The temperature sensor of the indoor unit senses room
temperature usually. Set the remote controller sensor
to sense the temperature around the remote controller.
Select items following the basic operation procedure
1
2
3
4
5
6
(
).
• Specify [32] for the CODE No. in Procedure
• Select the following data for the SET DATA in
4
Procedure
.
SET DATA
0000
0001
Remote controller
Not used
Used
sensor
(Factory default)
When
flashes, the remote controller sensor is
defective.
Select the SET DATA [0000] (not used) or replace the
remote controller.

Group control

In a group control, a remote controller can control up to
maximum 8 units.
• The wired remote controller only can control a group
control. The wireless remote controller is unavailable
for this control.
• For wiring procedure and wires of the individual line
(Identical refrigerant line) system, refer to "Electrical
Connection" in this Manual.
• Wiring between indoor units in a group is performed
in the following procedure.
• Connect the indoor units by connecting the remote
controller wires from the remote controller terminal
blocks (A, B) of the indoor unit connected with a
remote controller to the remote controller terminal
blocks (A, B) of the other indoor unit. (Non-polarity)
• For address setup, refer to the Installation Manual
attached to the outdoor unit.
– 14 –