9. Installation Information

9.1

Check Points

QUICK GUIDE
PIPING & ELECTRICAL SPECIFICATION
Indoor(ID) & Outdoor(OD) units:
Capacity
Possible Combination Patterns
(Btu/h)
Outdoor (OD): CU-2S18NBU-1
Indoor (ID): 2 UNITS OF
CS-S9NKUW-1
Outdoor (OD): CU-2S18NBU-1
Indoor (ID): 2 UNITS OF
16700
CS-S12NKUW-1
Outdoor (OD): CU-2S18NBU-1
Indoor (ID): 1 UNIT OF
CS-S9NKUW-1
+ 1 UNIT OF CS-S12NKUW-1
Example:
If total piping length of all installed indoor units is at 68.6 ft, the quantity of additional refrigerant should be 0.6 oz .......... (68.6 – 65.6) ft x 0.2 oz/ ft
= 0.6 oz.
Piping size
Refrigerant
Gas
Liquid
ø3/8"
ø1/4"
R410A
(ø9.52mm)
(ø6.35mm)
Min. pipe
Max.
Standard
Max.
length for
from
pipe
Elevation
each ID
OD to
length
unit
each ID
24.6 ft
49.2 ft
9.8 ft
82.0 ft
14
Min. total
Max.
pipe
Additional
Power
total
length for
refrigerant
supply
length
additional
gas
208/230V
60 Hz
164.0 ft
65.6 ft
0.2 oz / ft
MCA 20A
MOP 25A
Power
OD-ID
supply
connection
wire size
wire size
AWG12
AWG16