2. The temperature rise must be within the range specified on
the rating plate.
NOTE: Air temperature rise is the temperature difference
between supply and return air.
With a properly designed system, the proper amount of
temperature rise will normally be obtained when the unit is
operated at the rated input with the recommended blower speed.
If the correct amount of temperature rise is not obtained, it may
be necessary to change the blower speed. A higher blower speed
will lower the temperature rise. A slower blower speed will
increase the temperature rise.
NOTE: Blower speed must be set to give the correct air
temperature rise through the unit as marked on the rating plate.
External Static Pressure Check
The total external static pressure must be checked on this unit to
determine if the airflow is proper.

Blower Speed Adjustments

Refer to the wiring diagram in "Troubleshooting" to verify the
speed tap settings.
Depending upon the model, blower speeds are changed at the
indoor blower. The ignition control board has 4 blower speeds:
Low Heat, High Heat, Low Cool and High Cool.
NOTE: Fan Only energizes at Low Heat speed.
The WGGE45 models are equipped with X-13 motors. X-13
motors are constant torque motors with very low power
consumption. This motor is energized by 24VAC. Adjust the CFM
for the unit by changing the 24VAC leads to the speed terminal
block on the motor.
Heating
Speed
Lead
Tap
Definition
Color
T1
Low Speed
White
Heat
T2
High Speed
Brown
Heat
NOTE: Heating airflow must be adjusted to provide the
temperature rise shown on the rating plate. A higher speed tap
may not provide more airflow. Blower speeds are programmed to
deliver adequate airflow at rated external static pressure (ESP).
Refer to airflow table provided in the Product Data Book
applicable to your model for details.
Cooling
Speed
Lead
Tap
Definition
Color
T3
Low Speed
Purple
Cool
T4
High Speed
Yellow
Cool
T5
High Speed
Cool
High-Static

Blower Performance Data

WGGE4524A070M—Rise Range: 35º to 65º
Unit Static
0.1
0.2
st
T1—1
-
CFM 742
677
Stage
Watts 84
89
Heating
Speed
Amps 0.75 0.82
Rise 52
57
T2—2
nd
-
CFM 907
857
Stage
Watts 134
140
Heating
Speed
Amps 1.18 1.24
Rise 57
61
T3—
CFM 857
816
Cooling
Watts 116
126
Speed
Amps 1.04 1.16
T4—
CFM 907
857
Cooling
Watts 134
140
Speed
Amps 1.18 1.24
T5—
CFM 1,040 988
Cooling
Watts 185
198
Speed
Amps 1.33 1.40
WGGE4530A090M—Rise Range: 45º to 75º
Unit Static
0.1
0.2
st
T1—1
-
CFM 1,065 1,003 961
Stage
Watts 168
174
Heating
Speed
Amps 1.42 1.48
Rise 49
52
T2—2
nd
-
CFM 1,255 1,217 1,165 1,113 1,073 1,018 991
Stage
Watts 257
269
Heating
Speed
Amps 2.10 2.19
Rise 55
57
T3—
CFM 1,148 1,092 1,044 994
Cooling
Watts 170
176
Speed
Amps 1.55 1.66
T4—
CFM 1,148 1,092 1,044 994
Cooling
Watts 170
176
Speed
Amps 1.55 1.66
T5—
CFM 1,333 1,293 1,237 1,193 1,158 1,101 -
Cooling
Watts 304
314
Speed
Amps 2.41 2.48
0.3
0.4
0.5
0.6
0.7
631
575
526
-
-
97
101
111
-
-
0.90 0.92 1.01 -
-
62
X
X
-
-
814
761
727
678
-
149
154
165
169
-
1.32 1.33 1.41 1.47 -
64
X
X
X
-
760
721
670
629
-
131
140
145
155
-
1.18 1.25 1.31 1.39 -
814
761
727
678
-
149
154
165
169
-
1.32 1.33 1.41 1.47 -
949
903
871
824
-
208
213
222
228
-
1.42 1.49 1.55 1.58 -
0.3
0.4
0.5
0.6
0.7
913
855
814
749
185
195
202
212
218
1.55 1.62 1.69 1.76 1.82 1.87
54
57
60
63
69
274
285
296
302
313
2.21 2.30 2.36 2.41 2.48 -
59
62
64
68
70
929
811
763
184
194
210
222
224
1.72 1.77 1.89 1.99 2.03 2.07
929
811
763
184
194
210
222
224
1.72 1.77 1.89 1.99 2.03 2.07
321
333
341
345
-
2.54 2.71 2.77 2.78 -
0.8
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.8
713
227
72
-
-
-
715
236
715
236
-
-
-
17