Wiring the FH8000F (Furnace) Honeywell Enhanced Air
Cleaner
f. Attach the quick connect terminals to the furnace EAC-1 and EAC-2 spade connections, which are polarity
neutral.
g. Attach the ground ring to furnace chassis ground.
NOTE: The FH8000F Honeywell Enhanced Air Cleaner is to be powered by 120 VAC at 60 Hz.
NOTE: The Honeywell Enhanced Air Cleaner should only be powered when airflow is present. The furnace
control EAC spade connections provide power only when the furnace blower is operating. If EAC
connections are not available, an alternative airflow sensing mechanism such as the Honeywell
50027910-001 Differential Pressure Switch must be used to ensure the Honeywell Enhanced Air
Cleaner is only powered when airflow is present. Contact a local Honeywell distributor for information on
alternative airflow sensors.
Before proceeding to Startup and Operation on page 19:
I wired the Honeywell Enhanced Air Cleaner as instructed.
18
FH8000F Wiring is complete. Go to page 19.