Mitsubishi Electric City Multi PQHY-P72 Service Handbook page 70

Mitsubishi electric air conditioners city multi service handbook
Table of Contents

Advertisement

4. Connecting the BC controller
(1) Size of the pipe that fits the standard BC controller ports
P72 and P96 models
To heat source unit
*1
Reducer
(Standard
supplied parts)
Indoor
P18 model or below P24-P54 models P72-P96 models
The ports of the BC controller accommodates the pipes on P18-P54 models of indoor units.
To connect other types of indoor units, follow the procedure below.
Operation
Heat source unit
PQRY-P72TGMU-A
side
PQRY-P96TGMU-A
Indoor unit side
Connection: Brazed connection
BC controller
*2
Junction pipe kit
(Model name:
CMY-R160-J)
A
(Optional accessory)
Indoor
Indoor
High-pressure side (gas)
ø15.88 [5/8"] (Brazed connection)
ø19.05 [3/4"] (Brazed connection)
ø9.52 [3/8"] (Flare connection)
- 61 -
Branch joint (Model name:CMY-Y102S-G)
(Optional accessory)
B
Indoor
Indoor
Indoor
3*
Maximum of 3 units per port
Total capacity of P160 or below
(All units connected to the same port
must be in the same operating mode.)
Pipe sections
ø19.05 [3/4"] (Brazed connection)
ø22.2 [7/8"] (Brazed connection)
ø15.88 [5/8"] (Flare connection)
[ II Restrictions ]
Unit: mm [in]
Low-pressure side (gas)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents